Liebert DS User Manual

Page of 136
Piping Schematics
84
Figure 59 Piping schematic—water/glycol, semi-hermetic compressor models
Compressor
Muffler
Service
Valve
Cylinder
Unloader (s)
Evaporator 
Coil
Note: Schematic representation shown. This schematic does not imply or define elevations
and component location unless specifically noted ..
Two refrigeration circuits provided.  Single refrigeration circuit shown for clarity.
Solenoid
Valve
Expansion
Valve
Relief valve(s) 
supplied with 50Hz 
EU CE units rated
maximum 480 PSIG 
(33 Bar).
Paradenser® 
Condenser
Customer Heat Rejection
Liebert
Heat Rejection
Drycooler
(Glycol )
Glycol Pumps
Bypass Valve
Expansion 
Tank**
Hot Gas Reheat
Hose Bib *
Hose 
Bib *
Shutoff Valve *
Shutoff Valve *
Pressure Port *
Pressure 
Port *
Shutoff Valve *
Hose 
Bib *
Air Vents 
(typical) ***
Shutoff Valve *
Sensor
Aquastat
Sensing 
Bulb
Check Valves *
(on Dual Pump 
Systems only)
Flow Switch 
Supplied with Dual 
Pump Systems
Flow-Regulating 
Valve
Supply
Return
Return
Supply
Liquid
Suction
2-Way 
Regulating  
Valve
Optional
3-Way
Regulating  
Valve
Check Valve
Hot Gas Reheat 
Valve
Discharge
Liebert DS Unit
(and associated piping)
To Second 
Refrigeration 
Circuit
Service/Schrader (Access) Connection No Valve Core
Service/Schrader (Access) Connection With Valve Core
Factory Piping
Field  Piping
Optional Factory Piping
Service
Valve
External 
Equalizer
Sensing 
Bulb
Optional Dual Pump System Shown
Gate Valves *
Filter 
Dryer
Sight 
Glass
Cooling Tower 
and Pump 
System by 
Others
Return Supply
Components are not supplied by 
Liebert,  but are recommended for 
proper circuit operation and 
maintenance.
Field-installed at highest point
In system on return line to pumps
Locate at tops of all risers and any 
intermediate system high points
*
**
***
DPN00895
Rev. 2
For systems with drycoolers,