Delta Electronics DVPEN01-SL User Manual

Page of 54
Ethernet Communication Module DVPEN01-SL
 
DVP-PLC Application Manual 
46 
3.  Check “Enable Data Exchange” box. Enter IP address of PLC_A “192.168.0.4” in No. 1 Data 
Exchange Host IP column. Click on “OK” to complete the setting.   
 
 
4.  After all the settings in PLC_B are completed, compile the ladder diagram in the MPU and download it 
to PLC_B. See below for the program design: 
END
M1013
K100
K1
K1
K100
K100
K1
M2
M1
M1
SET
M1
TOP
K28
TOP
TOP
K29
K14
K13
K0
D100
K7
K100
K1
TOP
K1
SET
M2
M1
RST
K100
K1
M2
K14
D14
RST
M2
RST
M2
=  D14  K2
=  D14  K3
FROM
D100
T D
R
M1000
 
Explanations: 
• 
The data exchange will be executed every one second. 
• 
Write the communication address of the destination PLC in CR#28, and DVPEN01-SL will 
automatically detect by the previous setting that No. 1 IP is “192.168.0.4".