Delta Electronics EME-PG01 Leaflet

Page of 2
                                                                                                                                       
2007-07-09
5011659701-TPG1
 
EME-PG01
 
Pulse Generator Card for VFD-E Series Instruction Sheet
 
 
    Please thoroughly read this instruction sheet before installing option cards and putting them into use. 
    The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the 
most updated version at http://www.delta.com.tw/industrialautomation.
X
 
Layout
 
PG Card (EME-PG01) 
Pul se Fe ed ba ck
Pulse Outp ut
Y
 Installation
 
 
Make sure that the AC Motor Drive is powered off before operation. 
DO NOT insert or remove the card when the AC Motor Drive is 
powered on. 
 
Please mount the extension card as shown and fix it with the screw 
packed with the card. 
Screw torque: 
Maximum 2kgf-cm
 
 
Terminals Screw Torque: Maximum 2kgf-cm 
 
Wire Length 
Types of Encoder Output 
Maximum Length 
Wire
 
Gauge 
Voltage 
50m 
Open Collector 
50m 
Line Driver 
300m 
Complementary 
70m 
14 ~ 24 AWG 
(2.1 ~ 0.2 mm
)
NOTE
 
 
EME-PG01 needs additional power source DC 5 ~ 24V, as to 
details please refer to table of terminals descriptions. 
 
Only when the extension card is correctly installed on the AC 
Motor Drive, the extension card will be automatically detected. 
The parameters can be set in Group 13. If extension card is not 
installed, only parameters Group 0 ~ Group 10 can be set. 
Refer to Chapter 5: Parameters in the user manual for further 
details. 
Z
 Notes
 
 
Please use a shielded cable to prevent interference. Do not run 
control wires parallel to any high voltage AC power line (200 V and 
above).  
 
The wire length and signal frequency are in inverse proportion. 
 
Always use this product in a clean indoor location free from dust, 
corrosive gas and liquid. 
 
When the relays are used to switch inductive loads (relays, 
contactors, motors, etc), connect an RC network or Varistor parallel 
to the load to suppress voltage spikes. 
 
For safety, it is recommended to use fuses for the circuitry that is 
switched by the relays. The fuse specification must be within the 
specified contact limits. 
 
The ends of wires must be tinned or crimped. 
 
To avoid interference, route the extension card wires separately and 
as far away (at least 15cm) as possible from other control wires, 
motor wires and power wires, etc. Where these wires must cross 
each other, please make sure they are at a 90
angle. 
 
Always use and operate this product within the limit of its 
specifications.
 
[
 
Specification
 
 
Environmental 
Operating Temperature
-10
o
C to 50
o
C (non-condensing and not frozen)
Storage Temperature 
-20
o
 C to + 60
o
Ambient Humidity 
Less than 90%RH (non-condensing) 
Installation Altitude 
Below 1000m   
Vibration 
Below 20 Hz: Maximum 9.81 m/s
2
 (1G);   
20 ~ 50Hz: Maximum 5.88 m/s
2
 (0.6G) 
 
Terminals Descriptions 
Terminal Symbols
Descriptions
Vcc 
Input Voltage: DC 5 ~ 24V 
When the encoder output type is voltage output, 
input voltage is DC 12 ~ 24V 
0V 
Power source and input signal common 
A , 
B , 
A
B
 
Input signal from the encoder. Input type is selected 
by SW2. It can be 1-phase or 2-phase input.   
Maximum 300KP/sec 
A/O, B/O 
Output signal from the encoder.   
Open collector: max. output DC24V 50mA   
Grounding 
\
 
Types of Encoder Output
 
Types of Encoder 
Output
SW2
Wiring Diagram 
Voltage 
O/P
0V
VCC
OC
TP
 
Line driver
Q
Q
OC
TP
 
Complementary
O/P
0V
VCC
OC
TP
 
R(L1)
S(L2)
T(L3)
NFB
R
S
T
U(T1)
V(T2)
W(T3)
Motor
3~
VFD-E
OC
TP
A
B
Vcc
0V
A
B
A/O
B/O
RPM Meter
*The power source of RPM meter
 is supplied by  the customers. 
0V
A
B
A
PG
EME-PG01
 
DC
5~24V
+
-
GND
Vin
O/P
0V
VCC
OC
TP
 
R(L1)
S(L2)
T(L3)
NFB
R
S
T
U(T1)
V(T2)
W(T3)
Motor
3~
VFD-E
OC
TP
A
B
Vcc
0V
A/O
B/O
RPM Meter
*The power source of RPM meter 
 is supplied by the customers.
0V
A
B
A
B
PG
EME-PG01
 
DC
5~24V
+
-
GND
Vin
 
Open 
collector 
Note: Based on the design, the input signal terminals from 
the encoder should be connected to the terminals 
of
A
 and 
B
  on EME-PG01 card, not the terminals of 
A and B, so as to avoid damage to the encoder.