Delta Electronics VFD-F Series User Manual

Page of 161
 
VFD-F Series 
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 
2-1
CHAPTER 2    STORAGE AND INSTALLATION 
 
2.1 Storage 
The AC drive should be kept in the shipping carton before installation. In order to retain the 
warranty coverage, the AC drive should be stored properly when it is not to be used for an 
extended period of time.     
 
Ambient Conditions: 
 
Operation 
 
Air Temperature: -10
o
C to +40
o
C (14
o
F to 104
o
F)    
+50
o
C (122
o
F) without dust cover. 
Atmosphere pressure: 86 to 106 kPa 
Installation Site Altitude: below 1000m 
Vibration: Maximum 9.80 m/s
2
 (1G) at less than 20Hz 
Maximum 5.88 m/s
2
 (0.6G) at 20Hz to 50Hz 
 
 
Storage 
Temperature: -20
o
C to +60
o
C (-4
o
F to 140
o
F) 
Relative Humidity: Less than 90%, no condensation allowed 
Atmosphere pressure: 86 to 106 kPa 
 
 
Transportation 
 
Temperature: -20
o
C to +60
o
C (-4
o
F to 140
o
F) 
Relative Humidity: Less than 90%, no condensation allowed 
Atmosphere pressure: 86 to 106 kPa 
Vibration: Maximum 9.86 m/s
2
 (1G) at less than 20Hz, Maximum 5.88 
m/s
2
 (0.6G) at 20Hz to 50Hz 
 
Pollution Degree 
2: good for a factory type environment.