8-8
Group 4 Input Function Parameters
 
 
Parameters Functions 
Settings 
Factory 
Setting
Customer
 04-00 Multi-function 
Input 
terminal 
01 
 
 04-01 Multi-function 
Input 
terminal 
02 
 
 04-02 Multi-function 
Input 
terminal 
03 
 
 04-03 Multi-function 
Input 
terminal 
04 
 
 04-04 Multi-function 
Input 
terminal 
05 
 
 04-05 Multi-function 
Input 
terminal 
07 
 
 04-06 Multi-function 
Input 
terminal 
08 
 
 04-07 Multi-function 
Input 
terminal 
00: No function 
01: Multi-Speed terminal 1 
02: Multi-Speed terminal 2 
03: Multi-Speed terminal 3 
04: Multi-Speed terminal 4 
05: Reset (NO)   
06: Reset (NC)   
07: Jog operation (JOG) 
08: Accel/Decel disable 
09: Accel/Decel 2 selection 
10: Accel/Decel 3 selection 
11: B.B. (NO) input 
12: B.B. (NC) input   
13: Increase frequency 
14: Decrease frequency 
15: Emergency stop (NO) 
16: Emergency stop (NC)   
17: AVI(open), ACI1(close) 
18: KEYPAD(open), 
EXT(close) 
19: PID disable 
20: Auxiliary 1 input 
21: Auxiliary 2 input 
22: Auxiliary 3 input 
23: Auxiliary 4 input 
24: Auxiliary 5 input 
25: Auxiliary 6 input 
26: Auxiliary 7 input 
27: Motor No.1 output disable
28: Motor No.2 output disable
29: Motor No.3 output disable
30: Motor No.4 output disable
31: All motor output disable 
32: Run PLC program 
33: Pause PLC program 
09  
 
04-08  Digital Input Terminal Response 
Time 
01~20 01 
 
 
04-09  AVI Minimum voltage 
0.0~10.0V 
0.0  
 04-10 AVI 
Maximum 
voltage 
0.0~10.0V 
10.0  
 04-11 AVI 
Minimum 
frequency 
 
(percentage of Pr.1-00) 
0.00~100.00% 
0.00  
 04-12 AVI 
Maximum 
frequency 
 
(percentage of Pr.1-00) 
0.00~100.00% 
100.00
 
 
04-13  ACI1 Minimum current 
0.0~20.0mA 
4.0  
 
04-14  ACI1 Maximum current 
0.0~20.0mA 
20.0