Group 8 Special Parameters (Twice the value for 460V class)
 
 
Parameters Functions 
Settings 
Factory 
Setting
Customer
 
08-00  DC Brake Current Level 
00~100% 
00 
 
 
08-01  DC Brake Time during Start-up 0.0~60.0 Sec 
0.0 
 
 
08-02  DC Brake Time during Stopping 0.00~60.00 Sec 
0.0 
 
 
08-03  Start-point for DC Brake 
0.00~120.00 Hz 
0.00 
 
 08-04 Momentary 
Power 
Loss 
Operation Selection 
00: Disable 
01: Trace from top downward
02: Trace from bottom 
upward 
00  
 08-05 Maximum 
Allowable 
Power 
Loss Time 
0.1~5.0 Sec 
2.0 
 
 
08-06  Speed Search Time 
0.1~5.0 Sec 
0.5 
 
 08-07 Maximum 
Speed 
Search 
Current 
30~150% 110 
 
 
08-08  BB speed search method 
00: Trace from top downward
01: Trace from bottom 
upward 
00  
 
08-09  Auto Restart Times after Fault  00~10 
00 
 
 
08-10  Auto Restart Time after Fault 
00 to 60000 sec 
600 
 
 
08-11  Operation Frequency Inhibition 
1 UP 
0.00~120.00 Hz 
0.00 
 
 
08-12  Operation Frequency Inhibition 
1 DOWN 
0.00~120.00 Hz 
0.00 
 
 
08-13  Operation Frequency Inhibition 
2 UP 
0.00~120.00 Hz 
0.00 
 
 
08-14  Operation Frequency Inhibition 
2 DOWN 
0.00~120.00 Hz 
0.00 
 
 
08-15  Operation Frequency Inhibition 
3 UP 
0.00~120.00 Hz 
0.00 
 
 
08-16  Operation Frequency Inhibition 
3 DOWN 
0.00~120.00 Hz 
0.00 
 
 08-17 Automatic 
Energy-saving 00: 
Energy-saving 
operation 
disabled 
01: Energy-saving operation 
enabled 
00  
 08-18 Automatic 
Voltage 
Regulation 
(AVR) 
00: AVR function enabled 
01: AVR function disabled 
02: AVR function disabled for 
deceleration 
00  
a 08-19  Software Setting of the Brake
Level  
(the action level of the brake 
resistor) 
230V: 370~410VDC 
460V: 740~820VDC 
00:Disable 
380.0
760.0
 
a 08-20  Vibration Compensation Factor 00~1000 