Delta Electronics VFD-F Series User Manual

Page of 161
VFD-F Series
 
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
 
8-18
Group 10 PID Controls
 
 
Parameters Functions 
Settings 
Factory 
Setting
Customer
 
10-00  Input Terminal for PID 
Feedback 
00: No function 
01: Input via AVI   
02: Input via ACI1   
03: Input via ACI2 
04: Input via External 
Reference 
00  
 10-01 PID 
Control 
Detection 
Signal 
Reference 
0.0-6550.0 1000.0
 
 
10-02  PID Feedback Control Method 00: Negative feedback control
01: Positive feedback control
00  
 10-03 Proportional 
Gain 
(P) 
0.0~10.0 
1.0 
 
 10-04 Integral 
Time 
(I) 
0.00~100.00 
Sec 
1.00   
 10-05 Differential 
Time 
(D) 
0.00~1.00 
Sec 
0.00   
 
10-06  Upper Bound for Integral 
Control 
00~200% 100 
 
 
10-07  Primary Low Pass Filter Time  0.0~2.5 Sec 
0.0 
 
 
10-08  PID Feedback Signal Range 
0.0~6550.0 
600.0
 
 
10-09  PID Feedback Signal Fault 
Treatment Time 
0. 0~3600.0 Sec 
0.0: Disable 
0.0  
a
  10-10  PID Feedback Signal Fault 
Treatment 
00: Warn and RAMP stop   
01: Warn and COAST stop 
02: Warn and keep operating
01  
a
  10-11  PID Minimum Output 
Frequency 
0: By PID controller 
1: By AC drive 
01