AC Output Reactor Recommended Value
 
230V, 50/60Hz, 3-Phase 
Inductance (mH) 
kW HP 
Fundamental 
Amps 
Max. continuous 
Amps 
3% impedance 
5% impedance 
0.75 1 
12 
1.5 2 
12 
1.5 
2.2 3 
12 
18 
1.25 
2.5 
3.7 5 
18 
27 
0.8 
1.5 
5.5 7.5 
25 
37.5 
0.5 
1.2 
7.5 10 
35 
52.5 
0.4 
0.8 
11 15  55 
82.5 
0.25 
0.5 
15 20  80 
120 
0.2 
0.4 
18.5 25 
80 
120 
0.2 
0.4 
22 30  100 
150 
0.15 
0.3 
30 40  130 
195 
0.1 
0.2 
37 50  160 
240 
0.075 
0.15 
 
460V, 50/60Hz, 3-Phase 
Inductance (mH) 
kW HP 
Fundamental 
Amps 
Max. continuous 
Amps 
3% impedance 
5% impedance 
0.75 1 
12 
1.5 2 
6.5 
2.2 3 
12 
7.5 
3.7 5 
12 
18 
2.5 
4.2 
5.5 7.5 
18 
27 
1.5 
2.5 
7.5 10 
18 
27 
1.5 
2.5 
11 15  25 
37.5 
1.2 
15 20  35 
52.5 
0.8 
1.2 
18.5 25 
45 
67.5 
0.7 
1.2 
22 30  45 
67.5 
0.7 
1.2 
30 40  80 
120 
0.4 
0.7 
37 50  80 
120 
0.4 
0.7 
45 60  100 
150 
0.3 
0.45 
55 75  130 
195 
0.2 
0.3 
75 100  160 
240 
0.15 
0.23 
90 
125 160 
240 
0.15 
0.23 
110 
150 200 
300 
0.11 
0.185 
185 
250 320 
480 
0.75 
0.125 
220 
300 400 
600 
0.06 
0.105