Delta Electronics VFD-F Series User Manual

Page of 161
 
VFD-F Series 
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 
3-5
3.2 External Wiring 
R/L1 S/L2 T/L3
U/T1 V/T2 W/T3
B2
-
+/B1
E
E
BR
VF
DB
BR
EMI Filter
Power Supply
FUSE/NFB
Magnetic 
Contactor
Input AC 
Line Reactor
Zero-phase 
Reactor
B
ra
ke
 R
e
s
is
to
(O
p
ti
o
n
a
l)
B
ra
ke
 U
n
it
 
(O
p
ti
o
n
a
l)
Zero-phase 
Reactor
Output AC 
Line Reactor
Motor
 
 
 
 
 
 
 
Items Explanations 
Power 
supply 
Please follow the specific power 
supply requirements shown in 
Appendix A. 
Fuse/NFB 
(Optional) 
There may be an inrush current 
during power up. Please check the 
chart of Appendix B and select the 
correct fuse with rated current. Use 
of an NFB is optional. 
Magnetic 
contactor 
(Optional) 
Please do not use a Magnetic 
contactor as the I/O switch of the AC 
motor drive, as it will reduce the 
operating life cycle of the AC drive. 
Input AC 
Line Reactor
(Optional) 
Used to improve the input power 
factor, to reduce harmonics and 
provide protection from AC line 
disturbances (surges, switching 
spikes, short interruptions, etc.). AC 
line reactor should be installed when 
the power supply capacity is 500kVA 
or more or advanced capacity is 
activated. The wiring distance should 
be
  10m. Refer to appendix B for 
details. 
Zero-phase 
Reactor 
(Ferrite Core 
Common 
Choke) 
(Optional) 
Zero-phase reactors are used to 
reduce radio noise especially when 
audio equipment is installed near the 
inverter. Effective for noise reduction 
on both the input and output sides. 
Attenuation quality is good for a wide 
range from AM band to 10MHz. 
Appendix B specifies the zero-phase 
reactor. (RF220X00A) 
EMI filter 
(Optional) 
To reduce electromagnetic 
interference, please refer to 
Appendix B for more details. 
Brake 
Resistor 
(Optional) 
Used to reduce the deceleration time 
of the motor. Please refer to the chart 
in Appendix B for specific Brake 
Resistors. 
Output AC 
Line Reactor
(Optional) 
Motor surge voltage amplitude 
depends on motor cable length. For 
applications with long motor cable 
(>20m), it is necessary to install a 
reactor at the inverter output side.