Delta Electronics VFD-F Series User Manual

Page of 161
 
VFD-F Series 
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 
3-9
3.4 Control Terminals 
+24V
DCM
SINK/NPN Mode
Multi-function
Input Terminal
Internal Circuit
       
+24V
DCM
SOURCE/PNP Mode
Multi-function
Input Terminal
Internal Circuit
 
Terminal symbols and functions 
Terminal Symbols 
Terminal Functions Factory 
Settings 
FWD Forward-Stop 
command  
REV Reverse-Stop 
command  
EF External 
fault 
 
MI1 
Multi-function Input 1 
Factory setting: Multi-step speed command 1
MI2 
Multi-function Input 2 
Factory setting: Multi-step speed command 2
MI3 
Multi-function Input 3 
Factory setting: Multi-step speed command 3
MI4 
Multi-function Input 4 
Factory setting: Multi-step speed command 4
MI5 
Multi-function Input 5 
Factory setting: RESET 
MI6 
Multi-function Input 6 
Factory setting: JOG 
MI7 
Multi-function Input 7 
Factory setting: Accel/Decel prohibit 
MI8 
Multi-function Input 8 
Factory setting: Accel/Decel time switch 1 
+24V 
DC Voltage Source   
(+24V, 20mA), used for source mode. 
DCM 
Digital Signal Common 
Used as common for digital inputs and used 
for sink mode. 
RA 1 
Multi-function Relay1 
output (N.O.) a 
RB 1 
Multi-function Relay1 
output (N.C.) b 
RC 1 
Multi-function Relay1 
common 
RA 2 
Multi-function Relay2 
output (N.O.) a 
RB 2 
Multi-function Relay2 
output (N.C.) b 
RC 2 
Multi-function Relay2 
common 
1.5A(N.O.)/1A(N.C.) 240VAC 
1.5A(N.O.)/1A(N.C.) 24VDC 
Refer to Pr.03-00 to Pr.03-01