5.2 Group 1: Basic Parameters 
01 - 00 
Maximum Output Frequency 
     Factory Setting: 60.00
 Settings 
50.00~120.00Hz 
  This parameter determines the AC drives maximum output frequency.  All master frequency 
commands set by the keypad or analog inputs are limited by this parameter.  The analog 
commands (AVI, ACI1 and ACI2) may be scaled to correspond to the output frequency 
range.  (Please refer to 04-09~04-20.) 
01 - 01 
Maximum Voltage Frequency (Base Frequency) 
     Factory Setting: 60.00
 Settings 
0.10~120.00 
Hz 
  This parameter sets the frequency, where the maximum output voltage (Pr. 01-02) will be 
reached. The output frequency may exceed this setting, but the output voltage doesn’t 
increase beyond this point.  This parameter should be set according to the rated frequency 
of the motor as indicated on the motor nameplate.   
   If this parameter setting is smaller than the rated frequency of the motor, nuisance over 
current faults or damage to the AC drive may occur. 
  If this parameter setting is greater than the rated frequency of the motor, the motor will 
encounter torque loss. 
01 - 02 
Maximum Output Voltage 
Factory Setting: 220.0/440.0
 
Settings 
230V series: 0.1 ~ 255.0V 
460V series: 0.2 ~ 510.0V 
  This parameter determines the Maximum Output Voltage of the AC drive. This parameter 
setting should be set according to rated voltage of the motor as indicated on the motor 
nameplate. If rated voltage of the motor is 440V, this parameter must be set to 440V. If rated 
voltage of the motor is 380V, this parameter must be set to 380V. 
  If this setting is greater than the rated voltage of the motor, nuisance over current faults or 
damage to the AC drive may occur. 
01 - 03 
Mid-point Frequency 
     Factory Setting: 1.50
 Settings 
0.10~120.00 
Hz 
  This parameter sets the Mid-point Frequency of the V/f curve.   
  This parameter must meet the following argument.  Pr.1-01 >= Pr.1-03 >= Pr.1-05.