5.5 Group 4: Input Function Parameters 
04 - 00 
Multi-function Input terminal 1 
Factory Setting: 01
04 - 01 
Multi-function Input terminal 2 
Factory Setting: 02 
04 - 02 
Multi-function Input terminal 3 
Factory Setting: 03 
04 - 03 
Multi-function Input terminal 4 
Factory Setting: 04 
04 - 04 
Multi-function Input terminal 5 
Factory Setting: 05 
04 - 05 
Multi-function Input terminal 6 
Factory Setting: 07 
04 - 06 
Multi-function Input terminal 7 
Factory Setting: 08 
04 - 07 
Multi-function Input terminal 8 
Factory Setting: 09 
 Settings 
00~31 
 
Setting Functions 
Descriptions 
00 No 
function 
All unused terminals should be set to 00, to 
assure they have no effect on drive operation.
01 Multi-Speed 
terminal 
 
02 Multi-Speed 
terminal 
03 Multi-Speed 
terminal 
04 Multi-Speed 
terminal 
Allows selection of the 15 multi-step speeds. 
Please refer to 05-00 to 05-14 to program the 
15 step speeds. 
05 
Reset (NO)  
06 
Reset (NC)  
Clears (Reset) a fault and returns the AC drive 
to normal operation. 
07 
Jog operation (JOG) 
Enables the JOG command.  Works identical 
to the JOG key on the digital keypad.  
08 Accel/Decel 
disable 
Stops the acceleration or deceleration of the 
AC drive.  AC drive then maintains a constant 
speed.  
09 
Accel/Decel 2 selection 
10 
Accel/Decel 3 selection 
A corresponding terminal set to value 09 and 
closed selects Accel/Decel time 2.   A 
corresponding terminal set to value 10 and 
closed selects Accel/Decel time 3. 
Accel/Decel time 4 is selected when both 
terminals are closed. 
11 B.B. 
(NO) 
input 
12 
B.B. (NC) input  
Enables the base block (pause) function. 
Please refer to Pr.08-08, for base block 
functions. 
13 Increase 
Frequency 
14 Decrease 
Frequency 
Enables the external terminals to increase or 
decrease the Master Frequency command 
each time an input is received. Terminals are 
not active during a stop command.  
15 
Emergency stop (NO) 
16 
Emergency stop (NC)  
Generates an external fault (EF1). The 
function is identical to the external terminal 
(EF).