Delta Electronics VFD-F Series User Manual

Page of 161
VFD-F Series
 
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
 
5-30
5.7 Group 6: Protection Function Parameters  
06 - 00 
Over-voltage Stall Prevention 
Factory Setting: 390.0/780.0
 Settings 
230V series: 330.0 ~ 410.0VDC 
460V series: 660.0 ~820.0VDC 
00: Disable 
  This parameter selects the voltage level for the Over-Voltage Stall Prevention function.  
  During decelerations, the DC bus voltage may exceed its maximum allowable value due to 
motor regeneration. When this function is enabled, the AC drive will stop decelerating and 
maintain a constant output frequency.  The AC drive will only resume deceleration when the 
voltage drops below the preset value.  
  With moderate inertial loads, the over-voltage stall prevention will not occur and the 
deceleration time should be equal to Pr.1-10.   With high inertial loads, the AC drive will 
automatically extend the deceleration time due to the step function shown below.  If the 
deceleration time is critical for the application, then dynamic brake resistors should be 
used.  
Output frequency
Deceleration characteristic
when Over-voltage stall 
prevention enabled 
Frequency held
Deceleration Time
Time
 
 
06 - 01 
Over-current Stall Prevention during Acceleration 
Factory Setting:  120
 Settings 
20~150% 
Unit: 
1
  This parameter selects the percentage of allowable over-current during acceleration before 
the stall prevention is enabled.  
  During acceleration, the AC drive output current may increase abruptly and exceed the 
value specified by Pr.06-01 due to rapid acceleration or excessive load on the motor.  When 
this function is enabled, the AC drive will stop accelerating and maintain a constant output 
frequency.  The AC drive will only resume acceleration when the current drops below the 
value set in Pr.06-01 (please see the graph below). 
  When the over-current stall prevention is activated, the acceleration time of the AC drive will 
be longer than the time set in Pr. 01-09.