5.8 Group 7: AC Drive and Motor Parameters  
07 - 00 
Identity Code of AC Drive 
Factory Setting: ##
 Settings 
Display 
by 
model 
type 
  This parameter displays the AC drive model code.  
  This parameter is read-only.  
07 - 01 
Rated Current of AC Drive 
Factory Setting: ##
 Settings 
Display 
by 
model 
type 
  This parameter displays rated output current of the AC drive. The following chart may be 
used to look up the identity code, current, and hp of your drive. 
230V series 
KW 
0.75 1.5 2.2 3.7 5.5 7.5  11  15 18.5
22  30  37 
HP 
1  2  3  5  7.5 10 15 20 25 30 40 50 
Pr.07-00 
4  6  8  10 12 14 16 18 20 22 24 26 
Rated 
current 
(A)  5  7  11 17 25 33 49 65 75 90 120
145
Max. Carried Freq. 
10KHz 
9KHz 
6KHz 
Min. Carried Freq. 
4KHz 
3KHz 
2KHz 
Factory Setting 
9KHz 
6KHz 
4KHz 
460V series 
KW 
0.75 1.5  2.2  3.7 5.5 7.5 11 15 18.5 22 30 37 45  55  75
90 110 130 160 185 220
HP 1.0 
2.0 
3.0 
5.0 7.5 10 15 20 25 30 40 50 60 
75 
100 125 150 175 215 250 300
Pr.07-00 05 
07 
09 
11 13 15 17 19 21 23 25 27 29 
31 
33
35
37
39
41 43 45
Rated Current (A)  2.7  4.2 5.5 8.5 13 18 24 32 38 45 60 73 91 110 150 180 220 260 310 370 460
Max. Carried Freq. 
10KHz 
9KHz 
6KHz 
Min. Carried Freq. 
4KHz 
3KHz 
2KHz 
Factory Setting 
9KHz 
6KHz 
4KHz 
 This parameter is read-only. 
07 - 02 
Full-load Current of Motor 
a
 
Factory Setting:  100%
      
Settings 
30~120% 
Unit:  1
  This parameter selects the full load current of the motor.  
  Pr7-02 = (full load motor current / drive rated current)  
  Example: If the rated current of AC drive is 150A, full-load current of motor is 120A, then 
Pr.7-02 should be set to 80%.