LED Indicator & Trouble-shooting 
There are five LED indicators on RTU-DNET. POWER LED displays if the power of RTU-DNET is working 
normally. RUN LED displays the working status of RTU-DNET. ALRAM LED shows if RTU-DNET is operating 
normally. NS LED and MS LED display the communication connection status of RTU-DNET. 
6.1 POWER LED 
LED status 
Indication 
How to correct 
Off 
Power is abnormal. 
Make sure RTU-DNET is powered. 
Green light on 
Power is normal. 
-- 
6.2 NS LED 
LED status 
Indication 
How to correct 
Off 
No power or duplicate ID 
check has not completed.   
1.  Make sure RTU-DNET is powered. 
2.  Make sure the nodes on the bus are 
communicating normally. 
3.  Make sure at least 1 node or more are 
communicating on the network through 
RTU-DNET. 
4.  Check if the baud rate of RTU-DNET is the 
same as that of the master. 
Green light blinking 
On-line but not connected to 
DeviceNet 
-- 
Green light on 
On-line and connected to 
DeviceNet normally 
-- 
Red light blinking 
On-line but I/O connection 
timed-out 
-- 
Red light on 
Network error, cannot check 
duplicate ID, no network 
power or bus-off 
1.  Make sure all the devices have their unique 
node address. 
2.  Check the network for correcting media 
installation and baud rate. 
3.  Check if the node address of RTU-DNET is 
valid. 
4.  Check if the network power is normal. 
6.3 MS LED  
LED status 
Indication 
How to correct 
Off 
No power or off-line 
Make sure RTU-DNET is powered. 
Green light blinking 
Waiting for I/O data, no I/O 
data or PLC is in STOP 
mode. 
Switch the PLC to RUN status and start I/O data 
exchange. 
Green light on 
I/O data are normal. 
-- 
Red light blinking 
No network power; 
configuration error 
1.  Check if the network power is normal. 
2.  Reset the parameters in RTU-DNET. 
Red light on 
Hardware error 
Send your RTU-DNET back to the factory for repair.
6.4 ALARM LED  
LED status 
Indication 
How to correct 
Off Normal 
-- 
Red light blinking 
RTU-DNET detects low 
1.  Make sure RTU-DNET is powered.