Chapter 5 Parameters|VFD-S Series 
5-78
 
Revision August 2006, SE08, SW V2.61
 
the setting frequency of parameters, such as Max. operation frequency, 1
st
 speed and etc., 
they are still needed to set with actual value. 
 
P
A-02
I
A-03
A-01
+
+
+
+
Target
Value
Detection
Value 
Gain
D
A-04
A-05
A-07
Integration's 
Upper 
Bound 
Frequency
A-06
One-Time
Delay
Output Value
A-00
PID Frequency
Output 
Command
Limit
Frequency
Command
 
 
If the input range of sensor is 0~SI_max, output range is SO_min~SO_max and then  
 
Input
Per output
is 
SI_max
SO_max-SO_min
, set drive input to sensor output 
Set input range of drive is D_range= 10V(0~10V) or 16mA (4~20mA) that correspond to 0~1-00Hz 
and then 
Output
Per input
will be 
1-00
D_range
 
According to the display value of F and H = actual value 
¯A-13/1-00, and then 
Display value of F, H
Actual value
 
=A-13/1-00. If you want the result to be display value = sensor output and actual value = drive output, 
and then 
A-13
1-00
SI_max
SO_max-SO_min
A-01
100
1-00
D_range
=
X
A-13 =
SI_max
SO_max-SO_min
A-01
100
X
D_range
X
 
 
 
Example: 
Sensor: 0~6 psi input corresponds to 0~5V output drive AVI: 0~10V input corresponds to 0~60Hz, A-
01=100 
A-13 =
6
5-0
100
100
X
10
X
= 12