Chapter 7  Troubleshooting |VFD-S Series 
7-8 
Revision August 2006, SE08, SW V2.61 
7.11 Motor Stalls during Acceleration 
Motor stalls during 
acceleration
Check if acceleration
time is too short
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Increase setting time
Yes
Use special motor?
Reduce load or
increase the capacity
of AC  motor  drive
Check if the inertia 
of the motor and load 
is too high
Check for low voltage 
at input
Check if the load torque
is too high
Yes
Maybe AC motor drive has
malfunction or misoperation
due to noise. Please contact
DELTA
Increase torque compensation
Check if the torque 
compensation is suitable
Thicken or shorten the 
wiring between the 
motor or AC motor drive
Reduce load or
increase the capacity
of AC motor  drive
 
7.12 The Motor does not Run as Expected 
Check Pr. 01-01 thru Pr. 01-06 
and torque compensation 
settings
No
Yes
Yes
Yes
Yes
No
No
No
Adjust Pr.01-01 to Pr.01-06
and lower torque compensation
Run in low speed continuously
Is load too large
Please use specific motor
Reduce load or increase the 
capacity of AC motor drive
Check if output voltage of U, V, W 
 is balanced
Motor  has malfunction
Maybe AC motor drive has malfunction or misoperation
due to noise. Please contact DELTA.
Motor does not run
as expected