Chapter 5 Parameters|VFD-S Series 
5-10
 
Revision August 2008, SE09, SW V2.61
 
Group 9 Communication Parameters 
Pr. Explanation 
Settings 
Factory 
Setting
NOTE
9-00 
Communication  
Address 
d1 to d254 
d1 
 
d0: Baud Rate 4800 bps 
d1: Baud Rate 9600 bps 
9-01 Transmission Speed 
d2: Baud Rate 19200 bps 
d3: Baud Rate 38400 bps 
d1 
 
d0: Warn and Keep Operating 
d1: Warn and Ramp to Stop 
d2: Warn and Coast to Stop 
9-02 
Transmission Fault 
Treatment 
d3: Keep Operating without Warning
d0 
 
d0: Disable 
9-03 Time-out Detection 
d1 to d20: time setting (1 sec 
increment) 
d0 
 
d0: 7,N,2 (Modbus, ASCII) 
d1: 7,E,1 (Modbus, ASCII) 
d2: 7,O,1 (Modbus, ASCII) 
d3: 8,N,2 (Modbus, ASCII) 
d4: 8,E,1 (Modbus, ASCII) 
d5: 8,O,1 (Modbus, ASCII) 
d6: 8,N,2 (Modbus, RTU) 
d7: 8,E,1 (Modbus, RTU) 
9-04 
Communication 
Protocol 
d8: 8,O,1 (Modbus, RTU) 
d0 
 
 
Group A PID Parameters 
Pr. Explanation 
Settings 
Factory 
Setting
NOTE
A-00 
Input terminal for PID Feedback 
d0: Disable PID function 
d1: Negative PID feedback from 
external terminal (AVI) 0 to 
+10V 
d2: Negative PID feedback from 
external terminal (ACI) 4 to 
20mA 
d3: Positive PID feedback from 
external terminal (AVI) 0 to 
+10V 
d4: Positive PID feedback from 
external terminal (ACI) 4 to 
20mA 
d0 
 
A-01 
Gain over PID Detection value 
d0 to d999 
d100
 
A-02 
Proportional Gain (P) 
d0 to d999 
d100
 
A-03 
Integral Time (I) 
d0 to d999 
d100
 
A-04 
Derivative Control (D) 
d0 to d100 
d0 
 
A-05 
Upper Bound for Integral Control 
d0 to d100% 
d100
 
A-06 
Primary Delay Filter Time 
d0 to d999 
d0 
 
A-07 
PID Output Freq. Limit 
d0 to d110% 
d100
 
A-08 
Feedback Signal Detection Time 
d0.0 to d650 seconds 
d0.0