Delta Electronics VFD-S User Manual

Page of 185
Chapter 5 Parameters|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
5-17
 
5.3 Description of Parameter Settings 
Group 0: User Parameters                                    This parameter can be set during operation. 
0-00 
Identity Code of the AC Motor Drive 
 
Settings 
Read Only 
Factory setting:  d#
0-01 
Rated Current Display of the AC motor drive 
 
Settings 
Read Only 
Factory setting:  d ##.#
 
Pr. 0-00 displays the identity code of the AC motor drive. The capacity, rated current, rated 
voltage and the max. carrier frequency relate to the identity code. Users can use the following 
table to check how the rated current, rated voltage and max. carrier frequency of the AC 
motor drive correspond to the identity code. 
 
Pr. 0-01 displays the rated current of the AC motor drive. By reading this parameter the user 
can check if the AC motor drive is correct. 
115V/230V Series 
kW 0.2 
0.4 
0.75 1.5  2.2 
HP 
0.25 0.5 1.0 2.0 3.0 
Pr.0-00 
d0 d2 d4 d6 d8 
Rated Output Current (A)
1.6 2.5 4.2 7.5 11.0 
Max. Carrier Frequency
10kHz 
460V Series 
kW 0.4 
0.75 
1.5 
2.2 
HP 
0.5 1.0 2.0 3.0 
Pr.0-00 
d3 d5 d7 d9 
Rated 
Output 
Current 
(A)
1.5 2.5 4.2 5.5 
Max. Carrier Frequency
10kHz 
 
0-02 
Parameter Reset
  
 
 
 
 
Factory Setting:  d0
 
Settings  d9 
All parameters are reset to factory settings (50Hz, 220V/380V) 
 
 
d10 
All parameters are reset to factory settings (60Hz, 220V/440V) 
 
This setting allows the user to return all parameters to the factory default settings. 
 
0-03 
Start-up Display Selection 
 
 
 
 
Factory Setting: d0
 
Settings  d0  Display the frequency command value (LED F) 
 
 
 
d1  Display the actual output frequency (LED H)