                     Appendix C How to Select the Right AC Motor Drive | 
Revision Nov. 2008, VLE1, SW V1.03 
 C-5 
model, (to shorten deceleration time only) or increase the capacity for both the motor and 
the AC Motor Drive. 
C.3 How to Choose a Suitable Motor
 
Standard motor 
When using the AC Motor Drive to operate a standard 3-phase induction motor, take the 
following precautions: 
1. 
The energy loss is greater than for an inverter duty motor. 
2. 
Avoid running motor at low speed for a long time. Under this condition, the motor 
temperature may rise above the motor rating due to limited airflow produced by the 
motor’s fan. Consider external forced motor cooling. 
3. 
When the standard motor operates at low speed for long time, the output load must be 
decreased. 
4. 
The load tolerance of a standard motor is as follows: 
 
 
3  6    20                                 60
100
 
82
 
 
70
 
60
 
50
 
 
 
 
0  
60%
 
40%
 
25%
 
 
 
 
to
rq
ue(
%
)
continuous
Frequency (Hz)
Load duty-cycle
 
5. 
If 100% continuous torque is required at low speed, it may be necessary to use a special 
inverter duty motor. 
6. 
Motor dynamic balance and rotor endurance should be considered once the operating 
speed exceeds the rated speed (60Hz) of a standard motor. 
7. 
Motor torque characteristics vary when an AC Motor Drive instead of commercial power 
supply drives the motor. Check the load torque characteristics of the machine to be 
connected.