Delta Electronics VFD-VL User Manual

Page of 251
 Chapter 4 Parameters| 
Revision Nov. 2008, VLE1, SW V1.03                                                                                                                       4-21
 
 
00-02 
Parameter Reset  
Control 
mode
 
VF
 
VFPG
 
SVC
 
FOCPG TQCPG FOCPM
 
Factory setting:  0
 Settings 
No 
Function 
   1 
Read 
Only 
   8 
Keypad 
Lock 
 
 
9  All parameters are reset to factory settings (50Hz, 220V/380V) 
 
 
10  All parameters are reset to factory settings (60Hz, 220V/440V) 
 
When it is set to 1, all parameters are read only except Pr.00-00~00-07 and it can be used 
with password setting for password protection. 
 
This parameter allows the user to reset all parameters to the factory settings except the fault 
records (Pr.06-16 ~ Pr.06-21). 
50Hz: Pr.01-01 is set to 50Hz and Pr.01-02 is set to 230V or 400V. 
60Hz: Pr.01-01 is set to 60Hz and Pr.01-02 is set to 230Vor 460V.
 
 
When Pr.00-02=08, the KPVL-CC01 keypad is locked and only Pr.00-02 can be set. To unlock 
the keypad, set Pr.00-02=00. 
 
When Pr.00-02 is set to 1, Pr.00-02 setting should be set to 0 before setting to other setting. 
00-03 
Start-up Display Selection 
Control 
mode
 
VF
 
VFPG
 
SVC
 
FOCPG TQCPG FOCPM
 
Factory setting:  0
 Settings 
Display 
the 
frequency command value. (LED F) 
 
 
Display the actual output frequency (LED H) 
 
 
DC BUS voltage 
 
 
Display the output current (A) 
   4 
Output 
voltage 
 
 
Multifunction display, see Pr.00-04 
 
This parameter determines the start-up display page after power is applied to the drive. 
 
00-04 
Content of Multi-Function Display 
Control 
mode
 
VF
 
VFPG
 
SVC
 
FOCPG TQCPG FOCPM
 
Factory setting:  0
 
Settings  0  Display the output current in A supplied to the motor
O
U:
p
ut
E
ut
r
Cu r
t
en
E
S
E
E
EE
0
EE
A
. 0 m
E
ps
   1 
Reserved