Delta Electronics IFD9503 Leaflet

Page of 2
 
 
 
Warning 
 This instruction only provides introductory information on electrical specifications, functions, wiring, 
trouble-shooting and peripherals for IFD9503. Details of CANopen protocol are not included in this sheet. For more 
information on CANopen protocol, please refer to relevant reference or literatures.   
 IFD9503 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, 
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key 
or specific tools are required to open the enclosure) in case danger and damage on the device may occur. 
 IFD9503 is used for controlling the operating machine and equipment. In order not to damage it, only qualified 
professional staff familiar with the structure and operation of IFD9503 can install, operate, wire and repair it. 
 Please read this instruction sheet carefully before use and follow the sheet to operate IFD9503 in order to prevent 
damages on the device or injuries to staff.   
 DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 
the wiring again before switching on the power and DO NOT touch any terminal when the power is switched on. 
Make sure the ground terminal 
  is correctly grounded in order to prevent electromagnetic interference. 
 Introduction 
Thank you for choosing Delta IFD9503 CANopen slave station communication module. IFD9503 can be applied 
to the connection between CANopen network and Delta’s programmable logic controller, AC motor drive, servo 
drive, temperature controller and human machine interface. In addition, the custom function of IFD9503 allows 
the custom equipment with Modbus protocol to be connected to the CANopen network. 
 Functions & Services Supported 
 CAN2.0A protocol 
 CANopen DS301 V4.02 
 Process Data Object (PDO) 
 Network Management (NMT) 
 Service Data Object (SDO) 
 
 Product Profile & Outline 
 
Unit: mm 
Communication port 
Address setup rotary switch 
Function setup DIP switch 
Instructions on the DIP switch 
SCAN indicator 
RUN indicator 
ERROR indicator 
CANopen connector 
 
DIN rail 
 
DIN rail clip 
 
 Specifications 
 CANopen Connector 
Transmission method 
CAN 
Electrical isolation 
500V DC 
Type 
Removable connector (5.08mm) 
Transmission cable 
2 communication cables, 2 power cables and 1 shielded cable 
ENGLISH 
 Communication 
Message  type 
PDO, SDO, SYNC (synchronous object), Emergency (emergency object), NMT 
Series transmission 
speed 
10k, 20k, 50k, 125k, 250k, 500k, 800k, 1M bps (bits per second) 
Equipment type 
0 (Non-Profile) 
Company ID 
477 (Delta Electronics, Inc.) 
 Electrical Specifications 
Voltage 
11 ~ 25V DC 
Current 
28mA (typical), 125mA impulse current (24 VDC) 
 Environment
 
Standards 
IEC 61131-2, UL508 
Storage/operation 
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity); pollution degree 2 
Shock/vibration 
immunity 
International Standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & 
IEC 68-2-27 (TEST Ea) 
Interference immunity 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1,000MHz, 10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
Certificates 
CE, UL 
 Installation & Wiring 
 Install IFD9503 in an enclosure with sufficient space around it to 
allow heat dissipation (see the figure). 
 DO NOT place the I/O signal wires and power supply wire in the 
same wiring circuit.
 
IF D9503
D
D> 50mm
D
D
D
 
<1 .5 mm
28-12 AWG
 
 Use 28-12AWG (1.5mm) single or multiple core wire on I/O wiring 
terminals. See the figure for its specification. 
 The terminal screws shall be tightened to 4.75 kg-cm (4.12 in-lbs). 
 Use 60°C /75°C copper wires only.
 
 Components 
 CANopen Connector 
To connector with CANopen, use the connector enclosed with IFD9503 or any connectors you can buy in the 
store for wiring. 
PIN 
Signal 
Description 
V- 
0V DC 
CAN_L 
Signal- 
SHIELD 
Shielded cable 
CAN_H 
Signal+ 
V+ 
24V DC 
 
  1    2    3    4    5 
 Address Switch 
The two rotary address setup switches set up the node addresses on the 
CANopen network in hexadecimal form.   
Setup range: 01 ~ 7F (00 and 80 ~ FF are forbidden) 
01
2
3
4
5
6
7
8
9 A
B
C
D
E
F
H16
1
H16
0
01
2
3
4
5
6
7
8
9 A
B
C
D
E
F
 
Example:   
If you need to set the node address of IFD9503 to 26 (H1A), simply switch the corresponding rotary switch ×16
to “1” and the corresponding rotary switch ×16
0
 to “A”. 
Address Setting 
Description 
01 ~ 7F 
Valid CANopen node address 
00, 80 ~ FF 
Invalid CANopen node address 
Note: The changed value on the switch is only valid when IFD9503 is re-powered. When IFD9503 is operating, 
changing the set value of the communication address will be invalid. 
 Function Switch 
The DIP switch is to be used on the equipment connected to IFD9503, the 
selection of communication ports and setting up the communication speed of 
IFD9503 and the master station in CANopen. 
 
 Selecting  the Equipment  Connected  to  IFD9503 
PIN1  PIN2  PIN3 
Equipment 
  PIN1  PIN2  PIN3 
Equipment 
ON 
OFF 
OFF 
AC motor drive 
  ON 
OFF 
ON 
Human machine interface 
OFF 
ON 
OFF 
PLC 
  OFF 
ON 
ON 
Custom equipment 
ON 
ON 
OFF 
Temperature controller 
  ON 
ON 
ON 
For internal system use 
OFF 
OFF 
ON 
Servo  drive 
 
 
 
 
 
Example: 
If the equipment connected to IFD9503 is a Delta servo drive, you only need to switch PIN3 of the DIP switch to 
“ON”, PIN1 and PIN2 to “OFF” and re-power IFD9503. 
Note: The changed setting of the DIP switch is only valid when IFD9503 is re-powered. When IFD9503 is operating, 
changing the setting of the DIP switch will be invalid.   
 Selecting  IFD9503  Communication  Mode 
PIN4  PIN5 
Communication  Mode 
  PIN4  PIN5 
Communication  Mode 
OFF 
OFF 
RS-485 
 
ON 
OFF 
Incorrect setting 
ON 
ON 
RS-232 
  OFF 
ON 
Incorrect setting 
Note: The changed setting of the communication mode is only valid when IFD9503 is re-powered. When IFD9503 is 
operating, changing the setting of the communication mode will be invalid. 
 Setting  up Baud  Rate 
PIN6  PIN7  PIN8 
Baud Rate 
  PIN6  PIN7  PIN8 
Baud Rate 
OFF 
OFF 
OFF 
10kbps 
  OFF 
OFF 
ON 
250kbps 
ON 
OFF 
OFF 
20kbps 
 
ON 
OFF 
ON 
500kbps 
OFF 
ON 
OFF 
50kbps 
  OFF 
ON 
ON 
800kbps 
ON 
ON 
OFF 
125kbps 
 
ON 
ON 
ON 
1Mbps 
Note: The changed setting of the baud rate of CANopen is only valid when IFD9503 is re-powered. When IFD9503 is 
operating, changing the baud rate will be invalid 
 
 Communication Ports on IFD9503 
The communication ports on IFD9503 are used for the connection with other 
equipments (Delta PLC, AC motor drive, temperature controller, servo drive, 
HMI and custom equipments).   
PORT1
PORT2
 
 PORT  1 
PORT 1 Sketch 
Terminal No. 
Description 
N.C. 
GND 
DATA- 
DATA+ 
N.C. 
1
2
3
4
5
6
PORT1
 
N.C. 
Note: PORT 1 supports RS-485 communication mode only. 
 PORT  2 
PORT 2 Sketch 
Terminal No. 
RS-232 
RS-485 
N.C. 
N.C. 
RXD 
N.C. 
TXD 
DATA- 
N.C. 
N.C. 
GND 
N.C. 
N.C. 
N.C. 
N.C. 
N.C. 
N.C. 
DATA+ 
1
6
2
7
3
8
4
9
5
DB9   male
 
N.C. 
N.C. 
Note: PORT 2 supports RS-232 and RS-485 communication mode only. 
LED Indicators & Troubleshooting 
 RUN LED 
LED Status 
Indication 
How to deal with it 
OFF 
No power 
Check the power of IFD9503 and make sure the 
connection is normal. 
Green light single 
flash 
Stop 
--- 
Green light blinking 
Pre-operation 
--- 
Green light ON 
Operating 
--- 
Red light ON 
NODE-ID error 
Check if the setting of NODE-ID of IFD9503 is 
correct. 
 ERROR LED 
LED Status 
Indication 
How to deal with it 
OFF 
No error 
IFD9503 operation is normal. 
Red light double flash 
Error control event occurs. 
1. Check if the connection between IFD9503 and 
the master station is intact. 
2. Check if the communication between IFD9503 
and the master station is normal. 
LED Status 
Indication 
How to deal with it 
Red light ON 
BUS OFF 
1. Check if the BUS connection is normal. 
2. Re-power IFD9503. 
 Scan LED 
LED Status 
Indication 
How to deal with it 
OFF 
No power 
Check the power of IFD9503 and make sure the 
connection is normal. 
Green light flash 
The correct information of the 
equipment connected has not 
been  detected. 
Re-connect IFD9503 to the equipment. 
Green light ON 
The communication with the 
equipment connected is 
normal. 
 
Red light flash 
CRC check fails 
1. Check if the communication cable between 
IFD9503 and the equipment is correct. 
2. Check if there is electromagnetic interference 
nearby. 
Red light ON 
Connection fails, or no 
connection 
1. Check if the communication format of the 
equipment is correct. 
2. Check if IFD9503 and the equipment are correctly 
connected. 
3. Restart the connection and make sure the 
communication cable meets the specification. 
 
 
注意事項 
  本使用說明書僅提供電氣規格、功能規格、安裝配綫、故障排除及周邊裝置部份說明,該手册僅作爲 IFD9503
操作指南和入門參考,CANopen 協定的詳細內容這裏不作介紹。若想要瞭解更多關於 CANopen 協定的內容,
請參閱相關專業文章或書籍資料。 
 
本機爲開放型  (OPEN TYPE)  機殼,因此使用者使用本機時,必須將的安裝於具防塵、防潮及免於電擊∕衝
擊意外的外殼配線箱內。另必須具備保護措施(如:特殊的工具或鑰匙才可打開)防止非維護人員操作或意外
衝擊本體,造成危險及損壞。 
 
本産品用來控制運轉中的機械及設備。爲了避免損壞本産品,只有合格幷且熟悉本産品的結構及操作的專業人
員才可以安裝、操作、配綫及維護本産品。 
 
請務必仔細閱讀本使用手册,並依照本手册指示進行操作,以免造成産品受損,或導致人員受傷。 
 
交流輸入電源不可連接於輸入∕输出訊號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配綫。請勿
在上電時觸摸任何端子。本體上的接地端子    務必正確的接地,可提高産品抗干擾能力。 
  產品簡介 
謝謝您使用台達 IFD9503 模組,IFD9503 定義爲 CANopen 從站通訊模組,可用於 CANopen 網路和台達可程式
控制器、台達變頻器、台達伺服驅動器、台達溫控器以及台達人機界面的連接;此外,IFD9503 還提供自定義功
能,該功能用於連接 CANopen 網路和符合 Modbus 協定的自定義設備。 
 
支援的功能與服務 
 CAN2.0A 協定 
 CANopen DS301 V4.02 
  處理資料物件  (PDO) 
  網路管理物件  (NMT) 
  服務資料物件  (SDO) 
 
 
產品外觀及各部介紹 
   
尺寸單位: mm 
通訊埠 
位址設定開關 
功能設定開關  (DIP) 
功能設定開關說明 
SCAN
指示燈 
RUN
指示燈 
ERROR
指示燈 
CANopen
通訊連接器 
 
DIN
軌槽 
 
DIN
軌固定扣 
 
 
功能規格 
 CANopen 連接器 
傳輸方式 
CAN 
電氣隔離 
500V DC 
接頭 
可插拔式連接器  (5.08mm) 
傳輸電纜 
2
條通訊線、2 條電源線和 1 條遮蔽線 
繁體中文 
 
通訊 
資訊類型 
PDO
、SDO、SYNC(同步物件)、Emergency(緊急物件)、NMT 
串列傳輸速率 
支援 10k、20k、50k、125k、250k、500k、800k、1M bps(位元∕秒) 
設備類型 
0 (Non-Profile) 
廠商 ID 
477
(台達電子) 
 
電氣規格 
電壓規格 
11 ~ 25 VDC 
電流規格 
28mA
(典型值),125mA 衝擊電流  (24V DC) 
 
環境規格 
標準 
IEC 61131-2,UL508 
標準 
操作∕儲存環境 
儲存:-25°C ~ 70°C(溫度),5 ~ 95%(濕度) 
操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度),污染等級 2 
耐振動∕衝擊 
國際標準規範  IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 
(TEST Ea) 
雜訊免疫力 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 10V/m   
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
認證項目 
CE
認證、UL 認證 
 
盤內安裝及配線 
 IFD9503
在安裝時,請裝配於封閉式之控制箱內,其周圍應保持
一定之空間(如右圖所示),以確保 IFD9503 散熱功能正常。 
 
在配線時請勿將輸入點信號線與輸出點或電源等動力線置於同一
線糟內。
   
 
<1.5mm
28-12AWG
 
 
輸出/入配線端請使用 28-12AWG(1.5mm)單蕊祼線或多蕊線,端子規格
如左所示。 
 IFD9503
端子鏍絲扭力為 4.75 kg-cm(4.12 in-lbs)。 
 
只能使用 60°C/75°C 的銅導線。 
 
各部元件介紹 
 CANopen
通訊連接器 
與 CANopen 傳送線連接。可使用 IFD9503 隨機附帶的連接器或者市售的連接器進行配線。 
接腳 
訊號 
敍述 
V- 
0V DC 
CAN_L 
Signal- 
SHIELD 
遮蔽線 
CAN_H 
Signal+ 
V+ 
24V DC 
 
1    2    3    4    5