Delta Electronics VFD-VE Series User Manual

Page of 291
Chapter 6 Fault Code Information and Maintenance|                      
Revision August 2008, 03VE, SW V2.04 
6-11
„
  Printed circuit board and connector of main circuit
 
Maintenance 
Period 
Check Items 
Methods and Criterion 
Daily
Half 
Year
One 
Year
If there are any loose screws and 
connectors 
Tighten the screws and press the 
connectors firmly in place. 
 
{
 
If there is any peculiar smell and 
color change 
Visual inspection 
 
{
 
If there is any crack, damage, 
deformation or corrosion 
Visual inspection 
 
{
 
If there is any liquid is leaked or 
deformation in capacity 
Visual inspection 
 
{
 
 
„
  Cooling fan of cooling system
 
Maintenance 
Period 
Check Items 
Methods and Criterion 
Daily
Half 
Year
One 
Year
If there is any abnormal sound or 
vibration 
Visual, aural inspection and turn the 
fan with hand (turn off the power 
before operation) to see if it rotates 
smoothly 
 
 
{
If there is any loose screw 
Tighten the screw 
 
 
{
If there is any color change due to 
overheat 
Change fan 
 
 
{
 
„
  Ventilation channel of cooling system
 
Maintenance 
Period 
Check Items 
Methods and Criterion 
Daily
Half 
Year
One 
Year
If there is any obstruction in the 
heat sink, air intake or air outlet 
Visual inspection 
{