Delta Electronics VFD-VE Series User Manual

Page of 291
Chapter 2 Installation and Wiring| 
2-2 
 Revision August 2008, 03VE, SW V2.04
2.1 Wiring 
Users must connect wires according to the circuit diagrams on the following pages. Do not plug a 
modem or telephone line to the RS-485 communication port or permanent damage may result. The 
pins 1 & 2 are the power supply for the optional copy keypad KPV-CE01 only and should not be used 
for RS-485 communication. 
Figure 1 for models of VFD-VE Series (15 HP/11kW  and below)
VFD007V23A/43A-2, VFD015V23A/43A-2, VFD022V23A/43A-2, VFD037V23A/43A-2, 
VFD055V23A/43A-2, VFD075V23A/43A-2, VFD110V43B-2, VFD110V23A/43A-2
+2/B1
B2
Br ak e res istor
(optional)
+1
Jumper
DC choke
(optional)
Main c ircui t (power) terminals
Contr ol c ircuit  ter minals
Shielded l eads & Cable
Sw1
Sink
Source
F act ory set ting : 
SINK Mod e
Please refer to 
Fig ure 3 f or  wirin g 
of S INK m o de an d 
SO URCEm od e.
R(L1)
S(L2)
T(L3)
F us e/NF B(No Fuse B reaker)
SA
OF F
ON
MC
MC
RB
RC
Recommended Circuit 
 when power s uppl y 
is turned O FF by a 
fault output.
R(L1)
S(L2)
T(L3)
E
AVI
ACI
AUI
ACM
+10V
5K
3
2
1
Power supply
+10V 20mA
Master Fr equency
0 to 10V 47k 
Analog S ignal Common
E
U(T1)
V(T2)
W(T3)
IM
3~
RA
RB
RC
Motor
RS-485 s erial communication
1: +E V
2: G ND
3: SG -
4: SG +
5: NC
6: NC
E
DFM
DCM
Digital F requency Output
Ter minal
factory setti ng:  1:1 
Duty =50%, 10V DC
Digital Si gnal Com mon
Multi-function c ontact  output 1
(r elay)
factory setti ng:  fault  indi cation
MO1
MO2
MCM
Multi-function c ontact  output 3
(photocoupler)
Multi-function 
Photocoupler O utput
Multi-function c ontact  output 4
(photocoupler)
MRA
MRC
Multi-function c ontact  output 2
(r elay)
48VDC 50mA
factory setti ng: 
indicates that i t is running
DFM output s ignal selec tion
MI1
MI2
MI3
MI4
MI6
MI5
DCM
+24V
F WD/ST OP
REV/STO P
Multi-s tep 1
Multi-s tep 2
Multi-s tep 3
Multi-s tep 4
No function
Digital Si gnal Com mon
F ac tor y
setting
*  Don't apply the mains v oltage directly
   to  abov e terminals.
E
No function
REV
FWD
ACI cur rent/v oltage selection
AFM
ACM
Analog S ignal common
E
T he brake resis tor is built-in to model VF D110V43B.
NOTE
If the fault occur s, the 
contact will be O N to turn 
off the power and pr otect the power sy stem.
-
OC
T P
DFM Switch
Make  sure  that power is  OF F
befor e changing the switch
setting.
4~20mA/0~10V 
-10~+ 10V
0-20mA
0-10V
ACI Switch
Make sure that power is OF F
befor e changing  the  switch
setting.
0~ 10VDC/ 2mA
AF M analog output selection
Analog Multi- func tion Output Terminal
0-10V
0-20mA
AF M Switch
Make  sure  that power is  OF F
befor e changing  the  switch
setting.
For c ommunic ation,
it needs to use 
VF D- USB01/IF D8500 
to connect  to PC.