Delta Electronics DVP-SX Leaflet

Page of 2
 
 
 
Warning 
 
This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & 
wiring, troubleshooting and peripherals. Other detail information about programming and commands is compatible 
with SA/SC/SX series; please see PLC Application Manual. For more information about the optional peripheral, 
please see individual product manual.
 
 
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric 
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the 
enclosure, so as to avoid the hazard to users and the damage to the PLC. 
 
Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the PLC. 
Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the PLC is properly 
grounded 
. DO NOT touch terminals when power on.   
 Introduction 
Thank you for choosing DELTA’s PLC DVP series. The DVP-SX series is a 10-point (4DI+2DO+2AI+2AO) 
special main processing unit. Besides the same commands and functions as DVP-SA/SX/SC series, 2-CH 
12-bit analog voltage/current input and 2-CH 12-bit analog voltage/current output are all bipolar. There is 
built-in 2-digit 7-segment display corresponds to internal register directly to display PLC station or 
user-defined code. 
 Product Profile and Outline 
Status indicator: POWER, RUN, 
ERROR, BAT.LOW 
RUN/STOP switch 
2-digital 7-segment display 
Digital I/O terminal 
DIN rail clip 
Analog I/O terminals 
I/O point indicators 
COM1 (RS-232) (Rx) indicator 
COM2 (RS-485) (Tx) indicator 
10 
COM1 (RS-232)   
Communication port (Slave) 
 
Units: mm 
11  Nameplate 
12  Expansion port 
13 
Mounting  hold of the expansion 
unit 
14  DIN rail (35mm) 
15  Expansion unit clip 
16 
COM2 (RS-485)   
Communication port 
17  DC Power input 
18 
2 pin removable terminal   
(standard accessory) 
19 
Power input cable   
(standard accessory) 
20  Battery Cover 
21  Battery socket connection 
Battery replacement: Please change the battery within 3 minutes, or the 
internal data of the PLC (including the program area, RTC and latched 
registers) could be lost or destroyed. 
 
22  Battery mount 
ENGLISH 
 Electrical Specifications 
 Electrical Specifications 
 
     
Model   
    Item 
DVP10SX11R/T 
DVP08SM11N 
DVP08SN11R/T 
DVP08SP11R/T 
DVP16SP11R/T 
Power supply voltage 
MPU: 24V DC (-15% ~ 20%) (with DC input reverse polarity protection),   
Expansion Unit: supplied by the MPU 
Fuse 
2A / 250V AC 
Power Consumption 
5W 
1W 
1.5W 
1.5W 
2W 
Insulation Resistance 
> 5 M
Ω  at 500 V DC (Between all inputs / outputs and earth) 
Noise Immunity 
ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz~1GHz, 10V/m 
Grounding 
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N 
(All DVP units should be grounded directly to the ground pole). 
Environment 
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;   
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity); D/A output operation: 0°C ~ 50°C 
(temperature) 
Vibration / Shock 
Resistance 
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
Weight (approx.) (g) 
138 / 133 
64 
88 / 68 
90 / 70 
96 / 76 
Approvals 
 
 
 
 
Electrical Specification of Input Point 
Electrical Specification of Output Point 
Input Type 
DC (SINK or SOURCE) 
Output Type 
Relay-R 
Transistor-T 
Input Current 
24V DC 5mA 
Current 
Specification 
1.5A/1 point 
(5A/COM) 
0.3A/1 point @ 40°C; When the output of Y0 
and Y1 is high-speed pulse, Y0 and Y1 = 
30mA 
Off 
→  On,   
X0,X1: above 18.5V DC 
X2,X3: above 16.5V DC 
Voltage 
Specification 
Below 250V 
AC, 30V DC 
30V DC 
Active Level 
On
→Off,   
X0~X3 below 8V DC 
75VA 
(Inductive) 
Maximum 
Loading 
90 W 
(Resistive) 
9W/1 point 
When the output of Y0 and 
Y1 is high-speed pulse, Y0 
and Y1 = 0.9W (Y0 = 32kHz, 
Y1 = 10kHz) 
Responding 
Time 
About 10ms (An 
adjustment range of 0 ~ 20 
ms could be selected 
through D1020 and D1021) 
Responding 
Time 
About 10 ms 
Off
→On 20us 
On
→Off 30us 
Y0 and Y1 are specified 
points for high-speed pulse 
 Model Name & I/O Configuration 
Input 
Output 
Point 
Type 
Point 
Type 
Model 
Power 
DI  AI 
DI 
AI 
DO AO 
DO 
AO 
DVP10SX11R 
Relay 
DVP10SX11T 
24V 
DC 
+20% 
-15% 
DC24V/5 mA 
Sink or Source 
-20 ~ 20mA 
range(-1,000 ~ +1,000) 
-10 ~ +10V 
range(-2,000 ~ +2,000)  2 
Resistor 
-20 ~ 20mA 
(range:-2,000 ~ +2,000) 
-10 ~ +10V 
(range:-2,000 ~ +2,000) 
 Installation & Wiring 
3.1  PLC Mounting Arrangements and Wiring Notes 
Installation of the DIN rail: 
The DVP-PLC can be secured to a cabinet by using the 
DIN rail that is 35mm high with a depth of 7.5mm. When 
mounting the PLC on the DIN rail, be sure to use the 
end bracket to stop any side-to-side motion of the PLC, 
thus to reduce the chance of the wires being pulled 
loose. At the bottom of the PLC is a small retaining clip. 
To secure the PLC to the DIN rail, place it onto the rail 
and gently push up the clip. To remove it, pull down the 
retaining clip and gently pull the PLC away from the DIN 
rail. As shown on the right:   
 
When installing the DVP series 
PLC, make sure that it is 
installed in an enclosure with 
sufficient space (as shown 
below) to its surroundings so as 
to allow heat dissipation. 
DV P
M P
D
D
D
D
D > 50 mm
 
Wiring:
 
22-16AWG
< 1.5mm
 
1.  Please use 22-16AWG (1.5mm) wiring (either single or multiple core) for 
I/O wiring terminals. The specification for the terminals is as shown on 
the left. PLC terminal screws should be tightened to between 1.95 
kg-cm (1.7 in-lbs). Use 60/75°C copper conductor only. 
2.  I/O signal wires or power supply should not run through the same 
multi-wire cable or conduit. 
3.2  Wiring Notes 
 Power Input Wiring 
DVP-SX series input power supply is DC input. Please take a note of listed items when operating DVP-SX. 
Series. 
1.  Please make sure the power is at terminals 24V DC and 0V (power range is 20.4V DC ~ 28.8V DC). When 
voltage is lower than 20.4V DC, PLC will stop operating, all outputs will turn Off and ERROR LED will flash 
continuously. 
2.  If the power-off time is less than 10ms, the PLC still operates unaffectedly. If the power-off time is too long or 
the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the power is 
restored, the PLC will return to operate automatically. (There are latched auxiliary relays and registers 
inside of the PLC, please be aware when programming.) 
DC Input Type 
S/ S
X0
X1
X2
OV
24VDC
DC /DC
2A
5V
20.4V~28.8V
 
 Safety Wiring 
Since the PLC is in control of numerous devices, motion of either one device could affect the motion of other 
devices, therefore the breakdown of either one device would consequently be detrimental to the whole auto 
control system, and danger will thus be resulted. Please use the recommended wiring below for the power 
input: 
  Power supply for AC loads 
  Power Circuit Protection Fuse (3A)   
  Power On pilot indicator 
 
Emergency stop 
The machinery must provide a quick manual method 
disconnecting all system power. 
 
Circuit isolation device (System Power Disconnect) 
Utilize the electromagnetic contactor and the relay to be the 
isolation unit of the power circuit to prevent the possible 
instability of the system when the power is supplied on and off. 
  DVP PLC MPU (main processing unit) 
  Grounding 
MC
MC
N
L
1
1
2
3
4
5
6
8
G uard
Limit
7
MC
 
 
Power supply: 
AC: 100 ~ 240V AC, 50/60Hz 
DC: 24V DC 
 Input Point Wiring
 
The input signal of the input point is the DC power DC input. There are two modes of DC type wiring: SINK and 
SOURCE, defined as follows: 
Sink = Current flows into the common terminal S/S 
Source = Current flows out of common terminal S/S 
Sinkin g
S/S
X0
 
So urcing
S/S
X0
 
 
Loop Equivalent Circuit of Input Point 
Wiring Loop 
DC Type 
  (DC Signal IN)   
SINK Mode 
+24V
24G
S/S
X0
24VDC
SINK
+5V
 
+24V
OV
Sink  Type
X1
X2
S/S
X0
24VDC
 
Loop Equivalent Circuit of Input Point 
Wiring Loop 
DC Type 
  (DC Signal IN)   
SOURCE Mode 
+24 V
24 G
S/ S
X0
24VDC
SOUR CE
+5V
 
Source Type
X1
X2
S/S
X0
+24V
OV
24VD C
 
 Output Point Wiring 
Y0
RY
LED
C0
R E LAY O UT P U T
L O AD
P OW E R
DVP-**-**-11-R
 
Y0
LED
C 0
TRANSISTOR OUTPUT
LOAD
DVP- **-**-11-T
<0 .3 A
T
R
G
 
1.  There are two kinds of DVP-SX Series PLC output 
modules: Relay and Transistor. For relevant electrical 
specification, please refer to the function specification. 
2.  Be careful with the connection of the common 
terminals when wiring outputs. For example, when 
wiring DVP12SX11R, output terminal Y0 uses one 
common terminal C0, Y1 uses C1, as shown below: 
C0 Y0 C1 Y1
 
Action indication: When the output point is active, the 
corresponding indicator at the front will be on. 
3.  Isolated circuit: The optical coupler is used to isolate 
signals between PLC internal circuits and input 
modules. 
 Analog Input/Output Point Wiring
 
CH0
100K
250
-10V~+10V
V+
I+
COM
CH1
250
-20mA~+20mA
V+
I+
COM
*3
*2
AG
AG
Current input
Voltage input
Shielded*1
Shielded*1
100K
CH0
CH1
100K
100K
 
Note 1:   
Please isolate analog input and other power 
wiring. 
Note 2:   
If input signal is in current, please short out 
between V+ and I+ terminals. 
Note 3:   
If the noise interference from loaded input wiring 
terminal is significant, please connect a 
capacitor with 0.1 ~ 0.47µF 25V for noise 
filtering. 
V+
I+
COM
CH0
-10V~+10V
*5
CH0
V+
I+
COM
CH1
-20mA~20mA
CH1
24+
24-
DC24V
DC/DC
+15V
-15V
AG
voltage output
current output
AC drive, recorder,
scale valve...
shielding cable *1
shielding cable *4
AC drive, recorder,
scale valve...
terminal of
power module
class 3  grounding
(100  or less)
converter
 
Note 4:   
Please isolate analog output and other power 
wiring. 
Note 5:   
If the noise interference from loaded input wiring 
terminal is significant, please connect a 
capacitor with 0.1 ~ 0.47µF 25V for noise 
filtering. 
Note 6:   
Please connect 
  power module terminal and 
  analog output module terminal to system 
earth point and make system earth point be 
grounded or connects to machine cover. 
Warning:   
DO NOT wire to the No function terminal 
 
 
 
注意事項 
 
本使用說明書僅提供電氣規格、功能規格、安裝配線、故障排除及周邊裝置部份說明,其它詳細之程式設計
及指令與
SA/SX/SC
系列相容,詳細說明請見
PLC
技術手冊【程式篇】,選購之周邊裝置詳細說明請見該產
品隨機手冊。
 
 
本機為開放型(
OPEN TYPE
)機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊
/
擊意外之外殼配線箱內。另必須具備保護措施(如
特殊之工具或鑰匙才可打開)防止非維護人員操作或意
外衝擊本體,造成危險及損壞。請勿在上電時觸摸任何端子。
 
 
交流輸入電源不可連接於輸入
/
出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。本體上
之接地端子
 
 
務必正確的接地,可提高產品抗雜訊能力。
 
  產品簡介 
謝謝您採用台達
DVP
系列可程式控制器。
DVP-SX
機種為
10
點(
4DI+2DO+2AI+2AO
)特殊主機,除與
SA/SX/SC
主機具有相同的指令集及功能規格,並具有
2CH
12-bit
類比電壓
/
電流輸入及
2CH
12-bit
類比電壓
/
電流輸
出,同時均具有雙極性電壓
/
電流輸出能力。主機並內建
2
位數的七段顯示模組,直接對應內部暫存器,可用於
顯示站號或客戶自己定義的訊息代碼。
 
 
產品外觀及各部介紹 
電源、運行錯誤及電池低電壓
指示燈
 
RUN/STOP
開關
 
2
位數七段顯示模組
 
數位
I/O
端子
 
DIN
軌固定扣
 
類比
I/O
端子
 
輸出
/
輸入指示燈
 
COM1 (RS-232) 
通訊接收
(Rx) 
指示燈
 
COM2 (RS-485) 
通訊傳送
(Tx) 
指示燈
 
10 
COM1 (RS-232) 
通訊口
(Slave) 
 
尺寸單位:
mm 
11 
銘牌
 
12 
擴充機連接口
 
13 
擴充機定位孔
 
14  DIN
軌糟
  (35mm) 
15 
擴充機固定扣
 
16 
COM2 (RS-485) 
通訊口
(Master/Slave) 
17 
電源輸入口
 
18  2 pin 
脫落式端子(標準附件)
 
19 
電源輸入連接線(標準附件)
 
20 
電池蓋
 
21 
電池插座連接
 
電池安裝
電池安裝
電池安裝
電池安裝:
:更換電池時,請在
3
分鐘內完成,否則
PLC
內部資料(包含程式
區,萬年曆及停電保持暫存器)有可能會消失或被破壞。
 
 
22 
電池座
 
繁體中文
繁體中文
繁體中文
繁體中文    
  產品規格 
 
電氣規格 
 
 
 
機  種 
 
項  目 
DVP10SX11R/T 
DVP08SM11N 
DVP08SN11R/T 
DVP08SP11R/T 
DVP16SP11R/T 
電源電壓 
主機:24V DC(-15% ~ 20%)(具直流輸入電源極性反接保護),擴充機:由主機供應 
電源保險絲容量 
2A/250V AC 
消耗電力 
5W 
1W 
1.5W 
1.5W 
2W 
絕緣阻抗 
5MΩ
以上(所有輸出/入點對地之間  500V DC) 
雜訊免疫力 
ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz ~ 1GHz, 10V/m 
接地 
接地配線之線徑不得小於電源端 L,N 之線徑(多台 PLC 同時使用時,請務必單點接地) 
操作/儲存環境 
操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度);污染等級 2 
儲存:-25°C ~ 70°C(溫度),5 ~ 95%(濕度);D/A 輸出操作:0°C ~ 50°C(溫度) 
耐振動/衝擊   
國際標準規範  IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC68-2-27 (TEST Ea) 
重量(約, g) 
138 / 133 
64 
88 / 68 
90 / 70 
96 / 76 
認證 
 
 
 
 
輸入點電氣規格 
輸出點電氣規格 
輸 入
形 式 
直流(SINK 或 SOURCE) 
輸出 
形式 
繼電器-R 
電晶體-T 
輸 入
電 流 
24V DC 5mA 
電流 
規格 
1.5A/1
點(5A/COM) 
0.3A/1
點  @ 40°C 
高速脈波輸出時, Y0、Y1 為 30mA 
Off → On,   
X0
、X1 為 18.5V DC 以上 
X2
、X3 為 16.5V DC 以上 
電壓 
規格 
250V AC,30V DC
以下 
30V DC 
動 作
位 準 
On → Off,   
X0~X3
為 8V DC 以下 
75VA
(電感性) 
最大 
負載 
90W
(電阻性) 
9W/1
點 
高速脈波輸出時 
Y0
、Y1 為 0.9W 
(Y0:50KHz,Y1:10KHz) 
反 應
時 間 
約 10ms(由 D1020 及 D1021 可
作 0 ~ 20ms 的調整) 
反應 
時間 
約 10 ms 
Off → On 20us 
On → Off 30us 
Y0
、Y1 輸出為 
高速脈波輸出點 
 
機種型號與 I/O 配置 
輸入單元 
輸出單元 
點數 
形式 
點數 
形式 
機種 
電源 
DI  AI 
DI 
AI 
DO  AO 
DO 
AO 
DVP10SX11R 
繼電器 
DVP10SX11T 
24VDC 
+20% 
-15% 
DC24V/5 mA 
Sink
或 Source 
-20 ~ 20mA 
(
範圍:-1,000 ~ +1,000) 
-10 ~ +10V 
(
範圍:-2,000 ~ +2,000) 
電晶體 
-20 ~ 20mA 
(
範圍:-2,000 ~ +2,000) 
-10 ~ +10V 
(
範圍:-2,000 ~ +2,000)