Delta Electronics CME-LW01 Leaflet

Page of 2
                                                                                                                                     
2007-10-12
5011644001-LWT1
 
LonWorks Communication Module (CME-LW01) Instruction Sheet 
 Lonworks is a registered trademark of Echelon Corporation. 
 Please thoroughly read and understand the following contents to ensure correct use before operation. 
 The content of this instruction sheet may be revised without prior notice. Please consult our distributors or 
download the most updated version at http://www.delta.com.tw/industrialautomation
 
A. Introduction 
Device CME-LW01 is used for communication interface between 
Modbus and LonTalk. CME-LW01 needs be configured via 
LonWorks network tool first, so that it can perform the function on 
LonWorks network. No need to set CME-LW01 address. 
This manual provides instructions for the installation and setup for 
CME-LW01 that is used to communicate with Delta VFD-E 
(firmware version of VFD-E should conform with CME-LW01 
according to the table below) via LonWorks Network. The content 
of this instruction sheet may be revised without prior notice. 
Please consult our distributors or download the most updated 
version at http://www.delta.com.tw/industrialautomation.
 
 
Delta AC Drive 
Series 
Firmware Version 
VFD-E 
Version 2.02 or higher 
B. Dimensions 
5
7.
3
[2
.2
6]
72.2 [2.84]
59
.7
[2
.3
5]
9.
5
[0
.3
7]
3.5 [0.14]
34.8 [1.37]
SP
CME-LW 01
 
C. Specification 
Power supply 
16-30VDC, 750mW 
Communication 
Modbus in ASCII format, protocol: 9600, 7, N, 2 
LonTalk 
free topology with FTT-10A 78 Kbps 
LonTalk terminal 
4-pin terminal, wire gauge: 28-12 AWG, wire strip 
length: 7-8mm 
RS-485 port 
8 pins with RJ-45 
D. Wiring 
SP
CME-LW01
Power LED SP LED
Service LED
Service Pin
1: Reserved  
2: EV     
3: GND 
4: SG-            
5: SG+   
6: Reserved 
7: Reserved  
8: Reserved
LonTalk
1 2 3 4
LonTalk
 
 
 
Terminal definition for LonTalk system 
Terminal
Symbol 
Function 
 
 
These are twisted pair cables 
to connect to LonTalk system. 
Terminals 1 and 2 should be 
used as one group, and the 
same for terminals 3 and 4. 
E. LEDs 
Indications 
There are three LEDs in front panel of CME-LW01. If the 
communication is normal, power LED, SP LED should be green 
(red LED means abnormal communication) and service LED 
should be OFF. If LEDs display do not match, refer to user 
manual for details. 
 
 
Power LED 
State 
Description 
Corrective Actions 
Green LED
Power is on and 
CME-LW01 works 
 
LED is OFF
Power on or program is 
abnormal 
1. Check if power is 24V or 
plug is loose. 
2. Check if flash memory IC is 
well-inserted to the socket.
 
 
SP LED 
State 
Description 
Corrective Actions 
Green LED
It communicates to AC 
drive 
 
Blinked Green 
LED 
CME-LW01 reads default 
setting from AC drive 
 
Red LED 
Disconnect or time-out 
1. Check if cable is loose. 
2. Check if the communication 
protocol is properly set. 
 
 
Service LED 
State 
Description 
Corrective Actions 
LED blinks at 
1/2 Hz rate 
This is the normal 
situation for an 
un-configured device 
 
LED is OFF
Bad hardware device   
Check if anything wrong with 
power supply, clock or 
Neuron chip. 
LED is ON 
continuously, 
even when 
power is first 
applied to the 
device. 
Bad hardware device 
1.  Check if anything wrong 
with power supply, clock or 
Neuron chip. 
2.  Check if there is a short 
circuit between pin 17 and 
18. 
LED blinks at 
power-up, 
goes OFF, 
then ON 
solid. 
This is the normal 
situation for an 
application-less device. 
If the device is not an 
application-less, then it could 
be memory problems or 
application code errors. A 
self-test failure can also turn 
the LED ON solid. 
NOTE
 
Please download the XIF file and user manual at 
http://www.delta.com.tw/industrialautomation/