Delta Electronics DVP04TC-S Leaflet

Page of 2
http://www.delta.com.tw/industrialautomation/
                               
 
 
DVP04TC-S 
Thermocouple Sensors 
Instruction Sheet 
 
1   
WARNING 
  Always read this instruction thoroughly before using the DVP04TC-S. 
  Make sure that power is OFF before wiring.   
  This is an OPEN TYPE PLC.    The PLC should be kept in an enclosure away from airborne dust, 
humidity, electric shock risk and vibration.    Also, it is equipped with protective methods such as 
some special tools or keys to open the enclosure, in order to prevent hazard to users or damage 
the PLC.   
  Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may 
damage the PLC.    Check all the wiring prior to power up. 
    Do NOT touch internal circuit within 1 minute after power is OFF. 
    Make sure that the DVP04TC-S is properly grounded 
, to avoid any electromagnetic noise. 
2  
INTRODUCTION 
2.1  Model Explanation and Peripherals 
 
Thank you for choosing DELTA’s DVP Series PLC.  The DVP04TC-S allows the connection of 
four thermocouple sensors (Type J/K).    The DVP04TC-S series can read/write the data by using 
instructions FROM / TO via DVP-PLC SS/SA/SX/SC MPU program.    There are 49 CR (Control 
Register) in each module and 16 bits for each register.   
 
DVP04TC-S thermocouple sensor can update software version by RS-485.    Power supply and 
main processing units are sold separately.   
 
The DVP04TC-S works with both Centigrade and Fahrenheit.  The input resolution for 
Centigrade is 0.1 degrees and for Fahrenheit is 0.18 degrees. 
 
Nameplate Explanation 
P L C  m o d e l
Input power Supply Spec.
Analog Input /Output Module Spec.
Barcode, series and version
MODEL  
POWER  INPUT :
THERMOCOUPLES:
04 TC -S0 T50 200 01
VX.X
24Vdc  2W 
MADE  I N  XXXXX X
RESOLUTION:
14 BITS
TYPE J , K
 
 
Model Explanation 
Serial Number
Model
S: for SS/SA series MPU
XA: Analog input/output  mixed  module
Product Series
Input + Output points 
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors (PT-100) 
TC: Thermocouple sensors (Type J/K)
Production series
Production week
Production year (2005)
Production place (Taoyuan)
Serial number of version
Production Model
RT: Resistor Thermocouple(NTC)
 
2.2  Product Profile and Outline 
90.00
4.00
3.00
25.20
1
2
3
4
60.00
5
6
7
8
9
3
10
L+
L-
SLD
C
H
1
C
H
2
C
H
3
C
H
4
11
12
13
3.4
90.00
60.00
3.00
14
L+
L-
L+
L-
L+
L-
SLD
SLD
SLD
 
Unit: mm
 
1. Status indicator (Power, RUN and ERROR) 
8. Extension port 
2. Model Number 
9. Extension Clip 
3. DIN rail clip 
10. DIN rail location (35mm) 
4. I/O terminals 
11. RS-485 Communication port 
5. I/O point indicator 
12. Extension Clip 
6. Extension hole of the extension unit mounting 
pins 
13. DC Power input 
7. Specification Label 14. 
Extension 
port 
 
2.3 External 
wiring 
CH1
CH4
DC/ DC
5V
AG
+15V
-15V
AG
24+
24-
SLD
L-
L+
SLD
L-
L+
Converter
System
Class 3 Grounding
(100    of less)
terminal of
power module
Shielded*1
*2
*3
Shielded*1
Grounding
Thermocouple
+
-
100
MUX
Cold-junction
Compensation
Thermocouple
+
-
Note 1: Use only the wires that are 
supplied with your 
thermocouple sensor.  Tighten 
PLC terminal screws to a 
torque of 1.95 kg-cm (1.7 
in-lbs). 
Note 2: Terminal SLD is a grounding 
location for noise suppression. 
Note 3: Please connect 
 terminal of 
power supply module and 
 
terminal of DVP04TC-S 
thermocouple sensors module 
to system earth ground. 
Warning: DO NOT connect wires to the 
No Connection ( ) terminals.
Use copper conductor only, 
60℃
 
2.4    Terminals of analog module 
DVP04AD-S 
DVP02DA-S
DVP04DA-S
DVP04PT-S
DVP04TC-S
DVP06XA-S
DVP08RT-S
V+
I+
COM
FG
V+
I+
COM
FG
I+
COM
FG
V+
I+
COM
FG
V+
 
V+
I+
COM
FG
V+
I+
COM
FG
 
V+
I+
COM
FG
V+
I+
COM
FG
I+
COM
FG
V+
I+
COM
FG
V+
 
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
FG
FG
I-
L+
L-
I-
 
L+
L-
SLG
L+
L-
SLG
L+
L-
SLG
L+
L-
SLG
 
V+
I+
COM
V+
I+
COM
I+
COM
V+
I+
COM
V+
V+
I+
COM
V+
I+
COM
 
L+
L-
L-
L-
L+
L+
L-
L+
L+
L-
L-
L-
L+
L+
L-
L+
 
 
3  
STANDARD 
SPECIFICATIONS 
3.1 Function 
Specifications 
Platinum Temperature Module (04TC)
Centigrade (°C) 
Fahrenheit
 (°F) 
Power Supply Voltage 
24 VDC(20.4VDC~28.8VDC) ( –15%~+20%) 
Analog Input Channel 
4 channels per module 
Sensors Type 
J-type or K-type thermocouple 
Temperature Input Range 
J-type: -100°C~700°C 
K-type: -100°C~1000°C 
J-type: -148°F~1292°F 
K-type: -148°F~1832°F 
Digital Conversion Range 
J-type: K-1000~K7000 
K-type: K-1000~K10000 
J-type: K-3280~K12920 
K-type: K-1480~K18320 
Resolution 
14 bits(0.1°C) 14 
bits(0.18°F) 
Overall Accuracy 
±0.5% of full scale of 25°C(77°F), ±1% of full scale during 0~55°C 
(32~131
°F) 
Response Time 
250 ms  × channels 
Isolation Method 
Isolation between digital and analog circuitry. There is no isolation between 
channels. 
Digital Data Format 
2’s complement of 16-bit, (13 Significant Bits) 
Average Function 
Yes (CR#2~CR#5 may be set and the range is K1~K4096) 
Self Diagnostic Function 
Yes 
Communication Mode (RS-485) 
MODBUS ASCII/RTU Mode. Communication baud rate of 4800 / 9600 / 
19200 / 38400 / 57600 / 115200. For ASCII mode, date format is 7Bits, 
even, 1 stop bit (7 E 1). For RTU mode, date format is 8Bits, even, 1 stop 
bit (8 E 1). The RS-485 is disabled when the DVP04TC-S is connected in 
series to an MPU. 
Connection to a DVP-PLC MPU in 
Series 
When DVP04TC-S modules are connected to an MPU, the modules are 
numbered from 0 – 7. 0 is the closest to the MPU and 7 is the farthest. The 
Maximum number of modules is 8 modules and they do not occupy any 
digital I/O points of the MPU. 
3.2 Other 
Specification 
Power Specification 
Maximum Power Consumption 
2W at 24 VDC (20.4VDC~28.8VDC) ( -15 % ~ +20 %) 
 
Environment Condition 
Environment Condition 
Follow the DVP-PLC MPU. 
Static Electricity Prevention 
All places between terminals and ground comply with the spec. 
 
4
CR (Controlled Register) 
 
DVP04TC-S platinum temperature sensors 
Explanation 
CR
No.
RS-485 
Parameter 
address
Latched Register 
name b15 
b14 
b13 
b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
#0
H 4096 ○ 
Model type 
System used, DVP04TC-S model code = H 8B 
Reserved CH4 CH3 CH2 CH1 
#1
H 4097
  R/W Thermocouple 
type 
Example: Setting of CH1 
1.  b0: set 0 to use J-type and set 1 to use K-type 
2. b1: Reserved. 
3. b2: Reserved. 
#2
H 4098 ○  R/W  CH1 average number 
#3
H 4099 ○  R/W  CH2 average number 
#4
H 409A ○  R/W  CH3 average number 
#5
H 409B ○  R/W  CH4 average number 
The number of readings used for “average” temperature on channels CH1~CH4.   
Setting range is K1~K4096 and factory setting is K10. 
#6
H 409C ╳ 
CH1 average degrees(°C) 
#7
H 409D ╳ 
CH2 average degrees(°C) 
#8
H 409E ╳ 
CH3 average degrees(°C) 
#9
H 409F ╳ 
CH4 average degrees(°C) 
Average degrees for channels CH1~CH4.    (unit: 0.1 degrees C) 
#10
H 40A2 ╳ 
CH1 average degrees(°F) 
#11
H 40A3 ╳ 
CH2 average degrees(°F) 
#12
H 40A4 ╳ 
CH3 average degrees(°F) 
#13
H 40A5 ╳ 
CH4 average degrees(°F) 
Average degrees for channels CH1~CH4.    (unit: 0.1 degrees F) 
#14
H 40A8 ╳ 
Present temperature of 
CH1 (°C) 
#15
H 40A9 ╳ 
Present temperature of 
CH2 (°C) 
#16
H 40AA ╳ 
Present temperature of 
CH3 (°C) 
#17
H 40AB ╳ 
Present temperature of 
CH4 (°C) 
Present temperature of channels CH1~CH4. (unit: 0.1 degrees C) 
#18 Reserved 
#19
H 40AE ╳ 
Present temperature of 
CH1 (°F) 
#20
H 40AF ╳ 
Present temperature of 
CH2 (°F) 
#21
H 40B0 ╳ 
Present temperature of 
CH3 (°F) 
#22
H 40B1 ╳ 
Present temperature of 
CH4 (°F) 
Present temperature of channels CH1~CH4. (unit: 0.1degrees F) 
#23 Reserved 
#24
H 40AE ○
 
CH1 OFFSET Value 
#25
H 40AF ○
 
CH2 OFFSET Value 
#26
H 40B0 ○
 
CH3 OFFSET Value 
#27
H 40B1 ○
 
CH4 OFFSET Value 
Adjust offset value of channels CH1~CH4. The range is -1000~+1000 and 
factory setting is K0. (unit: 0.1 degrees C) 
#28~#29 Reserved 
#30
H 40B4 ╳ 
Error status 
Data register stores the error status, refer to fault code chart for details. 
#31
H 40B5
  R/W Communication 
address 
setting 
RS-485 communication address.   
Setting range is 01~255 and factory setting is K1 
#32
H 40B6 ○  R/W  Communication baud rate 
setting 
Communication baud rate (4800, 9600, 19200, 38400, 57600 and 115200 bps). 
b0: 4800 bps (bit/sec). 
b1: 9600 bps (bit/sec).    (factory setting) 
b2: 19200 bps (bit/sec). 
b3: 38400 bps (bit/sec). 
b4: 57600 bps (bit/sec). 
b5: 115200 bps (bit/sec). 
b6~b13: Reserved. 
b14: switch between low bit and high bit of CRC code (only for RTU mode) 
b15: RTU mode.   
b15 b14  b13  b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Definition of ERR 
LED 
CH4 CH3 CH2  CH1 
#33
H 40B7 ○  R/W  Reset to factory setting 
Example: Setting of CH1 
1. b0 Reserved 
2. b1 Reserved 
3. b2: Set to 1 and PLC will be reset to factory settings. 
Definition of ERR LED: b12~b15=1111(factory settings) 
1.  b12 corresponds to CH1:    when b12=1, scale exceeds the range or external 
contact has no connection, ERR LED flashes. 
2.  b13 corresponds to CH2: when b13=1, scale exceeds the range or external 
contact has no connection, ERR LED flashes. 
3.  b14 corresponds to CH3: when b14=1, scale exceeds the range or external 
contact has no connection, ERR LED flashes. 
4.  b15 corresponds to CH4: when b15=1, scale exceeds the range or external 
contact has no connection, ERR LED flashes. 
#34
H 40B4 ○ 
Software version 
Display software version in hexadecimal.    Example: H 010A = version 1.0A. 
#35~#48 System 
used 
 means latched.  
 means not latched. 
R means can read data by using FROM instruction or RS-485.   
W means can write data by using TO instruction or RS-485. 
Explanation: 
1. CR#0: The PLC model type.