Delta Electronics DVP-SA Leaflet

Page of 2
 
 
 
Warning 
 
This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & 
wiring. Other detail infromation about programming and intructions is compatible with SA/SX/SC series; please see 
PLC Application Manual. For more information about the optional peripherals, please see individual product 
instuction shee or “DVP-PLC Application Manual: Special module”. 
 
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric 
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the 
enclosure, in order to prevent hazard to users or damage the PLC. 
 
Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may damage the PLC. 
Check all the wiring prior to power up. To prevent any electromagnetic noise, make sure the PLC is properly 
grounded 
. Do NOT touch terminals when power on. 
    Introduction 
Thank you for choosing DELTA’s PLC DVP series. The DVP-SA series has a 12-points (8 input points + 4 
outputs) PLC main processing unit with multiple instructions for use. It also has an 8K Steps program memory 
to connect to every SA/SX/SC series extension unit, including digital I/O (Maximum 128 inpu/128 output 
extension points), analog module, etc. for various applications. Its power unit is separated from the MPU for 
better space utilization and easier installation. 
 Product Profile and Outline 
 
Unit: mm 
Battery replacement: Battery replacement must be finished within 3 minutes, or the internal data of the PLC 
(including the program area, RTC and latched registers) could be lost or destroyed. 
 
 
Status indicator: POWER, RUN, ERROR, BAT.LOW 
12  Extension port 
RUN/STOP switch 
13  Mounting hold of the extension unit 
VR0: Start-up by M1178/D1178 corresponding value 
14  DIN rail (35mm) 
VR1: Start-up by M1179/D1179 corresponding value 
15  Extension unit clip 
DIN rail clip 
16  COM2 (RS-485) communication port 
I/O terminals 
17  DC Power input 
I/O point indicators 
18  2 pin removable terminal (standard accessory) 
COM1 (RS-232) (Rx) indicator 
19  Power input cable (standard accessory) 
COM2 (RS-485) (Tx) indicator 
20  Battery cover 
10  COM1 (RS-232) port 
21  Battery socket connection 
11  Nameplate 
22  Battery mount 
ENGLISH 
 Specifications 
 
   
 
Model 
    Item 
DVP12SA11R/T 
Power supply voltage 
MPU: 24V DC (-15% ~ 20%) (with DC input reverse polarity protection) 
Fuse 
2A / 250V AC 
Power consumption 
3.5W 
Insulation resistance 
> 5M
Ω  at 500V DC (between all inputs / outputs and earth) 
Noise immunity 
ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz ~ 1GHz, 10V/m 
Grounding 
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L 
and N (All DVP units should be grounded 
directly to the ground pole). 
Environment 
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2 
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 
Vibration/shock resistance 
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
Weight (approx. g) 
158 
Certificates 
 
 
 
 
Input Point Electrical Specification 
Input type 
DC (SINK or SOURCE) 
Input current 
24V DC 5mA 
Off → On, 
X0, X1, 18.5V DC and above 
X2 ~ X7, 16.5V DC and above 
Active level 
On → Off, 
X0 ~ X7, below 8 V DC 
Response time 
About 10ms (an adjustment range of 0 ~ 20ms could be selected through D1020 and D1021) 
 
Output Point Electrical Specification 
Output type 
Relay-R 
Transistor-T 
Current specification 
1.5A/1 point (5A/COM) 
0.3A/1 point @ 40°C; When the output of Y0 and Y1 is high-speed 
pulse, Y0 and Y1 = 30mA 
Voltage specification 
Below 250V AC, 30V DC 
30V DC 
75VA (inductive) 
Maximum loading 
90W (resistive) 
9W/1 point 
When the output of Y0 and Y1 is 
high-speed pulse, Y0 and 
Y1 = 0.9W (Y0 = 32KHz, Y1 = 
10KHz) 
Response time 
About 10ms 
Off
→On 20us 
On
→Off 30us 
Y0 and Y1 are specified points 
for high-speed pulse 
Battery life: 
Temperature (
°C) 
25 
50 
70 
Life (year) 
Precision of calendar timer: 
At 0
°
C/32
°
F, less than -117 seconds error per month. 
At 25
°
C/77
°
F, less than 52 seconds error per month. 
At 55
°
C/131
°
F, less than -132 seconds error per month. 
 Model Name & I/O Configuration 
Input/Output 
Input Unit 
Output Unit 
Model 
Power 
Point 
Type 
Point 
Type 
Profile 
reference 
I/O Configuration 
DVP12SA11R 
Relay 
DVP12SA11T 
24V DC 
DC Sink or 
Source 
Transistor 
 
S/S
X0
X1
X2
X3
X4
X5
X6
X7
C0
Y0
C1
C2
Y1
Y2
Y3
 
 Installation & Wiring    
4.1 PLC Mounting Arrangements and Wiring Notes 
Installation of the DIN rail: 
The DVP-PLC can be secured to a cabinet by using 
the DIN rail that is 35mm high with a depth of 7.5mm. 
When mounting the PLC on the DIN rail, be sure to 
use the end bracket to stop any side-to-side motion 
of the PLC, thus to reduce the chance of the wires 
being pulled loose. At the bottom of the PLC is a 
small retaining clip. To secure the PLC to the DIN 
rail, place it onto the rail and gently push up the clip. 
To remove it, pull down the retaining clip and gently 
pull the PLC away from the DIN rail. As shown on the 
right: 
 
When installing the DVP series 
PLC, make sure that it is 
installed in an enclosure with 
sufficient space (as shown 
below) to its surroundings so as 
to allow heat dissipation. 
DV P
M P U
D
D
D
D
D > 50 mm
 
Wiring: 
22-16AWG
<1.5mm
 
1.  Please use 22-16AWG (1.5mm) wiring (either single or multiple core) for 
I/O wiring terminals. The specification for the terminals is as shown on 
the left. PLC terminal screws should be tightened to between1.95 kg-cm 
(1.7 in-lbs). 
2.  I/O signal wires or power supply should not run through the same 
multi-wire cable or conduit. Use 60/75°C copper Conductor only. 
4.2 Wiring Notes 
 Environment 
1.  DO NOT store the PLC in an atmosphere that is dusty, smoky, with metallic debris or corrosive or 
flammable gases. 
2.  DO NOT store the PLC in an environment with high temperature or high humidity. 
3.  DO NOT install the PLC on a shelf or on an unstable surface. 
 Power Input Wiring 
DVP-SA series input power supply is DC input. Please take a note of listed items when operating DVP-SA 
Series. 
1.  Please make sure the power is at terminals 24VDC and 0V (power range is 20.4 ~ 28.8V DC). When 
voltage is lower than 20.4V DC, PLC will stop operating, all outputs will be Off and ERROR LED will flash 
continuously. 
2.  If the power-cut time is less than 10ms, the PLC still operates unaffectedly. If the power-cut time is too 
long or the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the 
power is restored, the PLC will return to operation automatically. (There are latched auxiliary relays and 
registers inside of the PLC, please be aware when programming.) 
DC Input Type 
24V
2A
S/S
X0
X1
X2
20.4V~28.8V
0V
DC/DC
5V
 
 Safety Wiring
 
Since the PLC is used to control numerous devices, motion of either one device could affect the motion of other 
devices. Therefore the breakdown of a device would consequently be detrimental to the whole auto control 
system, thus the result is dangerous. Please use the recommended wiring below for the power input: 
M C
MC
N
L
1
1
2
3
4
5
6
7
8
G ua r d
Lim it
MC
 
 
 
Power supply for AC loads 
 
Power Circuit Protection Fuse (3A)   
 
Power On pilot indicator 
 
Emergency stop 
The machinery must provide a quick manual method disconnecting all system power. 
 
Circuit isolation device (System Power Disconnect) 
Utilize the electromagnetic contactor and the relay to be the isolation unit of the power circuit 
to prevent the possible instability of the system when the power is supplied on and off.   
 
DVP PLC MPU (main processing unit) 
 
Grounding 
 
Power supply: 
AC: 100 ~ 240V AC, 50/60Hz 
DC: 24V DC 
 Input Point Wiring
 
The DC power is used for DC input signal. 
Two types of DC wiring are used: SINK and SOURCE, defined as follows: 
 
Sink = Current flows into the common terminal S/S 
Source = Current flows out of common terminal S/S 
S in kin g
S /S
X 0
 
Sourcing
S/ S
X0
 
 
Input Point Loop Equivalent Circuit 
Wiring Loop 
DC Type 
  (DC Signal IN)   
SINK Mode 
+24 V
24G
S/S
X0
24V DC
SI NK
+5 V
 
+ 2 4V
O V
Sink  Type
X 1
X 2
S /S
X 0
24VDC
 
 
Input Point Loop Equivalent Circuit 
Wiring Loop 
DC Type 
  (DC Signal IN)   
SOURCE Mode 
+ 2 4V
2 4 G
S /S
X 0
24VDC
SOURCE
+ 5 V
 
Sou rc e Ty pe
X1
X2
S/S
X0
+24V
OV
24VD C
 
 Output Point Wiring
 
Y0
RY
LED
C0
LOAD
POWER
DVP-**-**-11-R
RELAY OUTPUT
 
DVP-**-**-11-T
TRANSISTOR  OUTPUT
LED
Y0
C0
LOAD
< 0.3A
T
R
G
 
1.  Two types of DVP-SA Series PLC output modules: Relay or Transistor. For the electrical specification, 
please refer to the function specification. 
2.  Please watch out the connection of common terminals while wire the outputs. For example, when wiring 
DVP12SA11R, output terminal Y0 uses one common terminal C0, Y1 uses C1, and Y2~Y3 share C2, as 
shown below: 
C0 Y0 C1 Y1 C2 Y2 Y3
 
Action indication: When the output point is active, the corresponding indicator at the front panel will be on. 
3.  Isolated circuit: The optical coupler is used to isolate signals between PLC internal circuits and input 
modules. 
 
 
注意事項 
 
本使用說明書僅提供電氣規格、功能規格、安裝配線部份說明,其它詳細之程式設計及指令與
SA/SX/SC
系列
相容,詳細說明請見
DVP-PLC
應用技術手冊【程式篇】,選購之週邊裝置詳細說明請見該產品隨機手冊或
DVP-PLC
應用技術手冊【特殊模組篇】。
 
 
本機為開放型
  (OPEN TYPE) 
機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊
/
衝擊
意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外
衝擊本體,造成危險及損壞。
 
 
交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請勿
在上電時觸摸任何端子。本體上之接地端子
 
 
務必正確的接地,可提高產品抗雜訊能力。
 
  產品簡介 
謝謝您採用台達
DVP
系列可程式控制器。
DVP-SA
系列為一
12
(8
輸入點
+4
輸出點
)PLC
主機,提供豐富的指
令集,並具有
8K Steps
的程式記憶體,可連接
SS/SA/SX/SC
系列全系列擴充機,包含數位輸入/輸出(最大輸入
/輸出擴充點數分別可達
128
點)、類比模組(
A/D
D/A
轉換及溫度單元)等各類機型,滿足各種應用場合。電
源單元與主機分離,體積小,安裝容易。
 
 
產品外觀及各部介紹 
   
尺寸單位:mm 
電池安裝
電池安裝
電池安裝
電池安裝:
:更換電池時,請在 3 分鐘內完成,否則 PLC 內部資料(包含程式區,萬年曆及停電保持寄存器)有可
能會消失或被破壞。 
 
 
電源、運行及錯誤指示燈 
12 
擴充機連接口 
RUN
/STOP 開關 
13 
擴充機定位孔 
VR0
:M1178 啟動/D1178 對應值 
14 
DIN
軌糟  (35mm) 
VR1
:M1179 啟動/D1179 對應值 
15 
擴充機固定扣 
DIN
軌固定扣 
16 
COM2 (RS-485) 
通訊口  (Master/Slave) 
輸出/入端子 
17 
電源輸入口 
輸出/入點指示燈 
18 
2 pin
脫落式端子(標準附件) 
COM1 (RS-232) 
通訊接收  (Rx)  指示燈 
19 
電源輸入連接線(標準附件) 
COM2 (RS-485) 
通訊傳送  (Tx)  指示燈 
20 
電池蓋 
10 
COM1 (RS-232) 
程式輸出/入通訊口 
21 
電池插座連接 
11 
銘牌 
22 
電池座 
繁體中文
繁體中文
繁體中文
繁體中文    
  電氣規格 
 
 
 
機種   
 
項目 
DVP12SA11R/T 
電源電壓 
主機:24V DC (-15% ~ 20%)(具直流輸入電源極性反接保護),擴充機:由主機供應 
電源保險絲容量 
2A/250V AC 
消耗電力 
3.5W 
絕緣阻抗 
5 M
Ω以上(所有輸出/入點對地之間  500V DC) 
雜訊免疫力 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 
1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 
接地 
接地配線之線徑不得小於電源端 L, N 之線徑(多台 PLC 同時使用時,請務必單點接地) 
操作/儲存環境 
操作:0°C~55°C(溫度),50 ~ 95%(濕度),污染等級 2 
儲存:-40°C ~ 70°C(溫度),5 ~ 95%(濕度) 
耐振動/衝擊   
國際標準規範  IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
重量(約, g) 
158 (g) 
 
輸入點電氣規格 
輸入形式 
直流(SINK 或 SOURCE) 
輸入電流 
24V DC 5mA 
Off → On, 
X0
、X1 為 18.5V DC 以上 
X2 ~ X7
為 16.5V DC 以上 
動作位準 
On → Off, 
X0 ~ X7
為 8V DC 以下 
反應時間 
約 10ms(由 D1020 及 D1021 可作 0 ~ 20 ms 的調整) 
 
輸出點電氣規格 
輸出點形式 
繼電器-R 
電晶體-T 
電流規格 
1.5A/1
點(5A/COM) 
0.3A/1
點  @ 40°C 
高速脈波輸出時, Y0、Y1 為 30mA 
電壓規格 
250V AC,30V DC
以下 
30V DC 
75VA
(電感性) 
最大負載 
90W
(電阻性) 
9W/1
點 
高速脈波輸出時 Y0、Y1 為 0.9W 
(Y0: 32KHz, Y1: 10KHz) 
反應時間 
約 10ms 
Off
→On 20us 
On
→Off 30us 
Y0
、Y1 輸出為 
高速脈波輸出點 
電池壽命
電池壽命
電池壽命
電池壽命:
 
溫度(°C) 
25 
50 
70 
壽命(年) 
萬年曆的精度
萬年曆的精度
萬年曆的精度
萬年曆的精度(
(秒
秒)
):
 
0°C/32°F
時,每月最大誤差
  -117
秒。
 
25°C/77°F
時,每月最大誤差
52
秒。
 
55°C/131°F
時,每月最大誤差
  -132
秒。