Delta Electronics DVP06AD-S Leaflet

Page of 2
 
 
Warning 
 Please read this instruction carefully before use. 
 DO NOT tough any terminal when the power is switched on. Switch off the power before wiring. 
 DVP06AD-S is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device 
(e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
 
 DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 
the wiring again before switching on the power.
   
 DO NOT touch any internal circuit in 1 minute after the power is switched off.   
 Make sure the groud terminal    is correctly grounded in order to prevent electromagnetic interference. 
 Introduction 
 Model Explanation & Peripherals 
 Thank you for choosing Delta DVP series. The analog signal input module DVP06AD-S is able to receive 6 
points of external analog signal inputs (both in voltage and current) and convert the signals into 14-bit 
digital ones. It is able to read and write the data in the module through FROM/TO instructions given by the 
program of DVP-PLC SS/SA/SX/SC/SV series MPU. There are 49 16-bit control registers in the module. 
 The user can select voltage or current output by wiring. Range of voltage output:  ±10V DC (resolution: 
1.25mV). Range of current output: 
±20mA (resolution: 5µA). 
 Product Profile & Outline 
1. POWER, ERROR, A/D indicator 
2. DIN rail clip 
3. Terminals 
4. Extension unit/module mounting hole 
5. Nameplate 
6. Extension unit/module connection port 
7. Extension unit/module fixing clip 
8. DIN rail (35mm) 
9. RS-485 communication port 
10. Extension unit/module fixing notch 
11. Power input port 
3
.0
0
9
0
.0
0
3.00
25.20
60.00
3.40
1
2
12
3
4
6
8
2
5
7
10
9
11
60.00
3
.0
0
 
Unit: mm 
12. Extension unit/module connection port 
 External Wiring 
CH1
104.7K
250
-10V~+10V
V+
I+
COM
CH1
100K
CH6
104.7K
250
-20mA~+20mA
V+
I+
COM
CH6
100K
*4
*2
AG
AG
24+
24-
 
100     or less)
(
DC/DC
+15V
-15V
AG
*3
Voltage input
Shielding cable*1
Shielding cable*1
Current input
System grounding
Eart h 
Connected to 
terminal
of the power module
Coverter
 
DVP06AD-S 
COM
V+
I+
COM
V+
I+
COM
V+
I+
COM
V+
I+
COM
V+
I+
COM
V+
I+
 
 
ENGLISH 
*1: When performing analog input, please isolate other power wirings. 
*2: When connecting to current signals, please make sure to short-circuit “V+” and “I+” terminals. 
*3: Please connect the 
  terminal on both the power module and DVP06AD-S to the system earth point and ground the 
system contact or connect it to the cover of power distribution cabinet. 
*4: If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the 
wiring to 0.1 ~ 0.47µF 25V capacitor. 
Note: DO NOT wire empty terminals 
 
 Specifications 
 Functions 
Analog/Digital   
(6A/D) module 
Voltage  input 
Current input 
Power  supply  voltage 
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%) 
Analog input channel 
6  channels/module 
Range of analog input 
±10V 
±20mA 
Range of  digital 
conversion 
±8,000 
±4,000 
Resolution 
14 bits (1
LSB
=1.25mV) 
13 bits (1
LSB
=5µA) 
Input impedance 
200KΩ or more 
250Ω 
Overall  accuracy 
±0.5% when in full scale (25°C, 77°F) 
±1% when in full scale in the range of 0 ~ 55°C, 32 ~ 131°F 
Response  time 
3ms × the number of channels 
Isolation 
Isolation between  digital area and  analog area. No isolation  among channels. 
Range of  absolute input 
±15V 
±32mA 
Digital  data  format 
13 significant bits out of 16 bits are available; in 2’s complement. 
Average  function 
Yes. Available for setting up in CR#2 ~ CR#7; range: K1 ~ K20. 
Self-diagnosis 
Upper and lower bound  detection/channel 
Communication  mode 
(RS-485) 
ASCII/RTU mode. 
Communication  speed:  4,800/9,600/19,200/38,400/57,600/115,200 
ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1) 
RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1) 
RS-485 cannot be used when connected to PLC MPU in series. 
When connected to 
DVP-PLC MPU in series 
The modules are numbered from 0 to 7 automatically by their distance from MPU. 
Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O 
points. 
 Others 
Power supply 
Max.  rated  power 
consumption 
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2W, supplied  by external  power. 
Environment 
Operation/storage 
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2. 
Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity). 
Vibration/shock 
immunity 
International  standards:  IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 
68-2-27 (TEST Ea) 
 Installation & Wiring 
 Mounting Arrangements and Wiring Notes 
 
Control Registers
 
CR
RS-485 
parameter 
address 
Latched 
Register content 
b15  b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 
#0 
H’4000 
Model name 
Set by the system. Data length: 8 bits (b7 ~ b0).   
DVP06AD-S model code=H’C8. 
Reserved 
CH6 
CH5 
CH4 
CH3  CH2 
CH1 
#1 
H’4001 
R/W  Input mode setting 
Input mode:  Default=H’0000. 
Mode 0: Voltage input (-10V ~ +10V) 
Mode 1: Voltage input (-5V ~ +10V) 
Mode 2: Current input (-12mA ~ +20mA) 
Mode 3: Current input (-20mA ~ +20mA) 
CR#1: The working mode of the 6 channels in the analog input module. There are 4 modes for each channel which can 
be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0=00) and CH2: mode 1 (b5 ~ b3=01), 
CH3: mode 2 (b8 ~ b6=10), CH4: mode 3 (b11 ~ b9=11), CH5: mode 0 (b11 ~ b9=00), CH6: mode 1 (b11 ~ b9=01), CR#1 
has to be set as H’04EA and the higher bits (b12 ~ b15) have to be reserved. Default value=H’0000. 
#2 
H’4002 
R/W 
CH2 
CH1 
#3 
H’4003 
R/W 
CH4 
CH3 
#4 
H’4004 
R/W 
CH1 ~ CH6 
Average times setting 
CH6 
CH5 
CR#2 ~ CR#4: Range of settings in CH1 ~ CH6: K1 ~ K20. The settings of average times of the signals at CH1 ~ CH6. 
Range: K1 ~ K20. For example, if the average time at CH1 is to be set as K10 and CH2 as K18, CR#2 has to be set as 
H’120A. CR#3 ~ 4 apply the same rule. The default setting of each channel=K10. Default settings of CR#2 ~ CR#4 are all 
H’0A0A. 
#6 
H’4006 
╳ 
CH1 input average 
#7 
H’4007 
╳ 
CH2 input average 
#8 
H’4008 
╳ 
CH3 input average 
#9 
H’4009 
╳ 
CH4 input average 
#10  H’400A 
╳ 
CH5 input average 
#11  H’400B 
╳ 
CH6 input average 
Average of input signals at CH1 ~ CH6 
CR#6 ~ CR#11: The average of the signals at CH1~CH6 obtained from the settings in CR#2~CR#4. For example, if the 
settings in CR#2~CR#4 is 10, the content in CR#6~CR#11 will be the average of the most recent 10 signals at CH1~CH6. 
How to install DIN rail 
DVP-PLC can be secured to a cabinet by using the DIN rail of 
35mm in height and 7.5mm in depth. When mounting PLC to 
DIN rail, be sure to use the end bracket to stop any side-to-side 
movement of PLC and reduce the chance of wires being loosen. 
A small retaining clip is at the bottom of PLC. To secure PLC to 
DIN rail, place the clip onto the rail and gently push it up. To 
remove it, pull the retaining clip down and gently remove PLC 
from DIN rail, as shown in the figure. 
 
Please install PLC in an 
enclosure with sufficient 
space around it to allow 
heat dissipation as shown 
in the figure. 
DVP
MP
D
D
D
D
D > 50 mm
 
 
 
Wiring 
22-16AWG
< 1.5 mm
 
 
1. Use 22-16AWG (1.5mm) single or multiple core wire on I/O wiring terminals. The 
specification of the terminal is shown in the figure on the left. The PLC terminal 
screws shall be tightened to 1.95 kg-cm (1.7 in-lbs).   
2. DO NOT place the I/O signal wires and power supply wire in the same wiring duct. 
3. Use 60/75 ºC copper wires only. 
CR
RS-485 
parameter 
address 
Latched 
Register content 
b15  b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 
#12  H’400C 
╳ 
CH1 input present value 
#13  H’400D 
╳ 
CH2 input present value 
#14  H’400E 
╳ 
CH3 input present value 
#15  H’400F 
╳ 
CH4 input present value 
#16  H’4010 
╳ 
CH5 input present value 
#17  H’4011 
╳ 
CH6 input present value 
Present value of input signals at CH1 ~ CH6 
#18  H’4012 
R/W  Adjusted OFFSET value of CH1 
#19  H’4013 
R/W  Adjusted OFFSET value of CH2 
#20  H’4014 
R/W  Adjusted OFFSET value of CH3 
#21  H’4015 
R/W  Adjusted OFFSET value of CH4 
#22  H’4016 
R/W  Adjusted OFFSET value of CH5 
#23  H’4017 
R/W  Adjusted OFFSET value  of CH6 
OFFSET settings at CH1 ~ CH6. Default=K0; Unit: LSB. 
When voltage input, range: K-4,000
LSB
 ~ K4,000
LSB
When current input, range: K-4,000
LSB
 ~ K4,000
LSB
Please refer to this instruction sheet when setting OFFSET and 
GAIN. 
#24  H’4018 
R/W  Adjusted GAIN value of CH1 
#25  H’4019 
R/W  Adjusted GAIN value of CH2 
#26  H’401A 
R/W  Adjusted GAIN value of CH3   
#27  H’401B 
R/W  Adjusted GAIN value of CH4 
#28  H’401C 
R/W  Adjusted GAIN value of CH5 
#29  H’401D 
R/W  Adjusted  GAIN value of CH6 
GAIN settings at CH1 ~ CH6. Default=K4,000; Unit: LSB. 
When voltage input, range: K-3,200
LSB
 ~ K16,000
LSB
When current input, range: K-3,200
LSB
 ~ K10,400
LSB
Please refer to this instruction sheet when setting OFFSET and 
GAIN. 
CR#18 ~ CR#29: Please note that: GAIN value – OFFSET  value=+800
LSB
 ~ +12,000
LSB
 (voltage) or +800
LSB
 ~ +6,400
LSB
 
(current) When GAIN – OFFSET is small (steep oblique), the resolution of input signal will be finer and variation on the 
digital value will be greater. When GAIN – OFFSET is big (gradual oblique), the resolution of input signal will be rougher 
and variation on the digital value will be smaller. 
#30  H’401E 
╳ 
Error status 
Register for storing all error status. 
See the table of error status for more information. 
CR #30: Error status value (see the table below): 
Error status 
Content 
b15 ~ b8 
b7 
b6 
b5 
b4 
b3 
b2 
b1 
b0 
Abnormal power supply 
K1 (H’1) 
Incorrect mode setting 
K4 (H’4) 
Offset/Gain error 
K8 (H’8) 
Hardware malfunction 
K16 (H’10) 
Abnormal digital range 
K32 (H’20) 
Incorrect average times setting 
K64 (H’40) 
Instruction error 
K128 (H’80) 
Reserved 
Note:  Each  error  status  is  determined  by  the  corresponding  bit  (b0  ~  b7)  and  there  may  be  more  than  2  errors 
occurring at the same time. 0=normal; 1=error   
 
#31  H’401F 
R/W  Communication address setting 
For setting RS-485 communication address. 
Range: 01 ~ 254. Default=K1. 
#32  H’4020 
R/W 
Communication speed (baud 
rate) setting 
For setting up RS-485 communication speed: 4,800/ 9,600/ 
19,200/ 38,400/ 57,600/ 115,200bps. ASCII data format: 7-bit, 
even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 
stop bit (8, E, 1).   
b0: 4,800 bps. b1: 9,600 bps (default).   
b2: 19,200 bps. b3: 38,400 bps.   
b4: 57,600 bps. b5: 115,200 bps.   
 
b6 ~ b13: Reserved.   
b14: High/low bit exchange of CRC checksum (only valid in 
RTU mode).   
b15: Switch between ASCII/RTU mode. 
Return to default 
CH6 
CH5 
CH4  CH3 
CH2 
CH1 
#33  H’4021 
R/W 
Return to default setting; 
OFFSET/GAIN tuning 
authorization 
Take the setting of CH1 for example: 
1. b0: Switch for upper/lower bound alarm on the input value for 
the channel. 0=disabled; 1=enabled (default). 
2. b1: OFFSET/GAIN tuning. 0=forbidden; 1=allowed (default). 
3. When b12 ~ b15=1, all values in CH1 ~ CH6 will return to 
default settings. b12 ~ b15 will return to 0 automatically after 
the setting is completed. 
CR for input mode, setting of average times, OFFSET value and GAIN value will be reset after returning to default settings. 
#34  H’4022 
Firmware version 
Displaying the current firmware version in hex, e.g. version 
1.00 is indicated as H’0100. 
#35 ~ #48 
For system use 
Symbols: 
○: Latched (when written in through RS-485 communication).   
╳: Non-latched. 
 
R: Able to read data by FROM instruction or RS-485 communication. 
W: Able to write data by TO instruction or RS-485 communication. 
LSB (Least Significant Bit): 1. For voltage input: 1
LSB
=10V/8,000=1.25mV.   
2. For current input: 1
LSB
=20mA/4,000=5µA. 
※  CR#0 ~ CR#34: The corresponding parameter addresses H’4000 ~ H’4022 are for users to read/write data 
by RS-485 communication. When using RS-485, the user has to separate the module with MPU first.   
a. Function codes: 03’H (read register data); 06’H (write 1 word datum to register); 10’H (write many words 
data to register). 
b. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written 
by MPU through TO/DTO instruction. 
 
Adjusting A/D Conversion Curve
 
Voltage input mode: 
CR#1 mode 0: 
GAIN=5V (4,000
LSB
). OFFSET=0V (0
LSB
). 
CR#1 mode 1: 
GAIN=6V (4,800
LSB
). OFFSET=2V (1,600
LSB
). 
GAIN: 
The voltage input value when the digital input value=4,000. 
Range: -3,200
LSB
 ~ +16,000
LSB
OFFSET: 
The voltage output value when the digital input value=0. 
Range: -4,000
LSB
 ~ +4,000
LSB
+
0 0
+ 4, 000
-4,
0
00
10V
Vol tage in put
- 8,
0
00
-6V
-10V
6 V
5V
2V
0
M od e 1
M o de 0
GAIN
OFFSET
d
ig
it
a
lo
u
tp
u
t
 
GAIN - OFFSET:  Range: +800
 LSB
 ~ +12,000
 LSB
Current input mode: 
CR#1 mode 2: 
GAIN=20mA (4,000
LSB
). OFFSET=4mA (800
LSB
). 
CR#1 mode 3: 
GAIN=20mA (4,000
LSB
). OFFSET=0mA (0
LSB
). 
GAIN: 
The current input value when the digital input value=+4,000. 
Range: -3,200
LSB
 ~ +10,400
LSB
OFFSET: 
The current input value when the digital input value=0. 
Range: -4,000
LSB
 ~ +4,000
LSB
+ 4, 000
current input
- 4,
0
00
-12mA
-20mA
4mA
0
Mode 2
Mode 3
OFFSET
20mA
GAIN
  GAIN - OFFSET:  Range: +800
 LSB
 ~ +6,400
 LSB
The user can adjust the OFFSET/GAIN curves according to the actual needs by changing the OFFSET value 
(CR#18 ~ CR#23) and GAIN value (CR#24 ~ CR#29). 
 
注意事項 
  請在使用之前,詳細閱讀本使用說明書。 
  請勿在上電時觸摸任何端子。實施配線,務必關閉電源。 
  本機為開放型  (OPEN TYPE)  機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/衝擊
意外之外殼配線箱內。另必須具備保護措施  (如:  特殊之工具或鑰匙才可打開)  防止非維護人員操作或意外衝
擊本體,造成危險及損壞。 
  交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。 
  輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。 
  本體上之接地端子 
 
務必正確的接地,可提高產品抗雜訊能力。 
 
產品簡介 
  說明及週邊裝置 
  謝謝您採用台達 DVP 系列產品。DVP06AD-S 類比信號輸入模組可接受外部 6 點類比信號輸入(電壓或電
流皆可),將之轉換成 14 位元之數位信號。透過 DVP-PLC SS/SA/SX/SC/SV 主機程式以指令 FROM/TO 來
讀寫模組內之資料,模組內具有 49 個 CR (Control Register)
 
暫存器,每個暫存器為 16 bits。 
  使用者可經由配線選擇電壓輸入或電流輸入。電壓輸入範圍  ±10V DC (解析度為 1.25mV)。電流輸入範圍 
±20mA (
解析度為 5µA)。 
  產品外觀及各部介紹 
1. 
電源、錯誤及運行指示燈 
2. DIN
軌固定扣 
3. 
端子 
4. 
擴充機/擴充模組定位孔 
5. 
銘牌 
6. 
擴充機/擴充模組連接口 
7. 
擴充機/擴充模組固定扣 
8. DIN
軌糟
 
(35mm) 
9. RS-485
通訊口 
10. 
擴充機/擴充模組固定槽 
11. 
電源輸入口 
3
.0
0
9
0
.0
0
3.00
25.20
60.00
3.40
1
2
12
3
4
6
8
2
5
7
10
9
11
60.00
3
.0
0
 
尺寸單位:mm 
12. 
擴充機/擴充模組連接 
  外部配線 
CH1
104.7K
250
隔離線*1
電壓輸入
-10V~+10V
V+
I+
COM
CH1
1 00K
CH6
104.7K
250
隔離線*1
電流輸入
-20mA~ +20mA
V+
I+
COM
CH6
1 00K
* 4
*2
AG
AG
24+
24-
接至電源模
組之
 
接地
(
100     
)
接地阻抗
以下
DC/DC
轉換器
+15 V
-15V
AG
*3
系統接地點
 
DVP06AD-S 
CO M
V+
I+
CO M
V+
I+
CO M
V+
I+
CO M
V+
I+
CO M
V+
I+
CO M
V+
I+
 
 
繁體中文 
註 1:類比輸入請與其他電源線隔離。 
註 2:如果連接電流信號時,V+
 
及 I+
 
端子請務必短路。 
註 3:請將電源模組之    端及 DVP06AD-S 類比信號輸入模組之 
 
端連接到系統接地點,再將系統接點作第
三種接地或接到配電箱之機殼上。 
註 4:如果輸入電壓有漣波造成配線受雜訊干擾時請連接 0.1 ~ 0.47µF 25V 之電容。 
注意:空端子    請勿配線。
 
 
規格 
  功能規格 
類比/數位   
(6A/D) 
模組 
電壓輸入  (Voltage input) 
電流輸入  (Current input) 
電源電壓 
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%) 
類比訊號輸入通道 
6
通道/台 
類比輸入範圍 
±10V 
±20mA 
數位轉換範圍 
±8,000 
±4,000 
解析度 
14 bits (1LSB=1.25mV) 
13 bits (1LSB=5µA) 
輸入阻抗 
200KΩ
以上 
250Ω 
總和精密度 
 
±0.5%  在  (25°C, 77°F)  範圍內滿刻度時。 
±1%  在  (0 ~ 55°C, 32 ~ 131°F)  範圍內滿刻度時。 
響應時間   
3ms × 
通道數 
隔離方式 
數位區與類比區有隔離,通道間未隔離。 
絕對輸入範圍 
±15V 
±32mA 
數位資料格式 
16
位元二補數,最大有效位 13 bits。 
平均功能 
有  (CR#2 ~ CR#7 可設定,範圍 K1 ~ K20) 
自我診斷功能 
上下極限偵測/通道 
通訊模式  (RS-485) 
有,包含 ASCII/RTU 模式,通訊速率可選  (4,800/9,600/19,200/38,400/57,600 
/115,200)
,ASCII 模式資料格式固定為 7 bits、偶位元、1 stop bit (7, E, 1),RTU
模式資料格式固定為 8 bits、偶位元、1 stop bit (8, E, 1)。當與 PLC 主機串接時,
RS-485
通訊無法使用。 
與 DVP-PLC 主機串接說明 
模組編號以靠近主機之順序自動編號由 0 到 7,最大可連接 8 台且不佔用數位 I/O
點數。 
  其他規格 
電源規格 
額定最大消耗功率 
直流 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2W,  由外部電源供應。 
環境規格 
操作/儲存環境 
操作:0°C ~ 55°C (溫度),50 ~ 95% (濕度),污染等級  2; 
儲存:-25°C ~ 70°C (溫度),5 ~ 95%(濕度) 
耐振動/衝擊   
國際標準規範  IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 
(TEST Ea)