Delta Electronics DVP02DA-S Leaflet

Page of 2
http://www.delta.com.tw/products/plc.asp
        
         
DVP02DA-S 
                               
 DVP02DA-S
                   
Analog Output Module 
                                                                             
Instruction Sheet
 
 
WARNING 
  Please carefully read this instruction thoroughly prior to use the DVP02DA-S. 
  The DC input power must be OFF before any maintenance. 
  This is an OPEN-TYPE built-in DVP02DA-S, and the DVP02DA-S is certified to meet the safety 
requirements of IEC 61131-2 (UL 508) when installed in the enclosure to prevent high 
temperature, high humidity, exceessive vibration, corrosive gases, liquids, airbome dust or 
metallic particles. Also, it is equipped with protective methods such as some special tool or key 
to open the enclosure, so as to avoid the hazard to users or any damage to the DVP02DA-S. 
  Do not connect the AC power to any of the input/output terminals, or it may the DVP02DA-S. 
Make sure that all the wiring is well conducted prior to power On. 
  Do not touch the internal circuit for at least 1 minute after the power is Off. 
  Make sure that DVP02DA-S is properly grounded 
, to avoid any electromagnetic noise.
 
 
INTRODUCTION 
2.1  Model Explanation and Peripherals 
 
Thank you for choosing DELTA DVP PLC Series. The analog output module of DVP02DA-S series 
can read/write the data of analog output module by using commands FROM / TO via DVP-PLC 
SS/SA/SX Series MPU program. The analog output module receives 2 group 12-bit digital data 
from PLC MPU and converts it into 2 points analog output signal (voltage or current). There are 49 
CR (Control Register) in each module and there are 16 bits in each register. 
 
The software version of DVP02DA-S analog output module can be updated via RS-485 
communication. Power unit and module are separate. Size is small and easy to install. 
 
Users can select output either voltage or current via wiring. Voltage output range is 0V ~ +10V DC 
(resolution is 2.5 mV). Current output range is 0mA ~ 20mA (resolution is 5 µA). 
 
Nameplate Explanation 
02DA-S0T3250003
VX.XX
20.4VDC ~ 28.8VDC
MADE  IN  XXXXX X
P L C  m o d e l
2.5 mV or  5    A
 0V ~ + 10V or  0mA ~ +20mA
Input power Supply Spec.
Analog Input /Output Module Spec.
Barcode, series and version
 
 
Model Explanation 
Serial Number
Model
S: for SS series MPU
P: for EP series MPU
H: for EH series MPU 
XA: Analog input/output mixed module
Product Series
Input + Output points 
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors (PT-100) 
TC: Thermocouple sensors (Type J/K)
Production series
Production week
Production year (2004)
Production place (Taoyuan)
Serial number of version
Production Model
RT: Resistor Thermocouple
HC: Input module of high-speed counter
PU: single axis positioning unit
 
2.2  Product Profile and Outline 
90.00
4.00
3.00
25.20
1
2
3
4
60.00
5
6
7
8
9
3
10
FG
V+
I+
COM
C
H
1
FG
V+
I+
COM
C
H
2
11
12
13
3.4
90.00
60.00
3.00
14
 
Unit:mm 
1. Status indicator (Power, RUN and ERROR) 
8. Expansion port 
2. Model name 
9. Expansion unit clip 
3. DIN rail clip 
10. DIN rail (35mm) 
4. I/O terminals 
11. RS-485 Communication port 
5. I/O point indicator 
12. Mounting rail of the expansion unit 
6. Mounting hole of the expansion unit 
13. DC Power input 
7. Nameplate 
14. Expansion port 
 
2.3 External 
wiring 
Voltage output
0V ~ 10V
V+
2
FG
COM
V+
FG
I+
CH1
CH2
24+
24-
AG
+15V
-15V
DC/DC
converter
3
System 
Grounding
Class 3 Grounding
(100     or less)
 Ω
DC24V
I+
Current output
0mA~20mA
COM
CH1
CH2
Isolation wire    1
Isolation wire    1
AC drive, recorder,
scale valve...
AC drive, recorder,
scale valve...
terminal of 
power module
 
Note 1: Please isolate analog output and other 
power wiring. 
Note 2: If noise interferes from loaded input wiring 
terminal is significant, please connect a 
capacitor with 0.1~0.47µF 25V for noise 
filtering.  
Note 3: Please connect 
 power module 
terminal and 
  analog output module 
terminal to system earth point and make 
system earth point be grounded or 
connects to machine cover.   
Warning: DO NOT wire to the No function terminal 
 
2.4    Terminal of analog module layout   
DVP04AD-S 
DVP02DA-S 
DVP04DA-S 
DVP04PT-S 
DVP04TC-S 
DVP06XA-S 
DVP08RT-S 
V+
I+
COM
FG
V+
I+
COM
FG
I+
COM
FG
V+
I+
COM
FG
V+
 
V+
I+
COM
FG
V+
I+
COM
FG
 
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
 
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
FG
FG
I-
L+
L-
I-
 
L+
L-
SLD
L+
L-
L+
L-
L+
L-
SLD
SLD
SLD
 
V+
I+
COM
V+
I+
COM
I+
COM
V+
I+
COM
V+
V+
I+
COM
V+
I+
COM
 
L1+
L1-
FG
L3+
L3-
L2-
L2+
L4-
L4+
L51
L5-
FG
L7+
L7-
L6-
L6+
L8-
L8+
 
 
 
STANDARD SPECIFICATIONS 
3.1 Specifications 
Digital/Analog (2D/A) Module
Voltage Output 
Current Output 
Power Supply Voltage 
24 VDC (20.4VDC~28.8VDC) (–15%~+20%) 
Analog Input Channel 
2 channels / each module 
Analog Output Range 
0~10V 0~20mA 
Digital Data Range 
0~4000 0~4000 
Resolution  
12 bits (1
LSB
=2.5 mV) 
12 bits (1
LSB
=5 µA) 
Output Impedance 
0.5Ω or lower 
Overall Accuracy 
±0.5% of full scale of 25℃(77℉)  
±1% of full scale during 0~55℃ (32~131℉) 
Response Time 
3 ms  × channels 
Max. Output Current 
20mA (1KΩ~2MΩ) 
 
Tolerance Carried Impedance 
 
0〜500Ω 
Digital Data Format 
2’s complementary of 16-bit, 13 Significant Bits 
Isolation Method 
Isolation between digital area and analog area. But no isolation 
among channels. 
Protection 
Voltage output has short circuit protection but a long period of short 
circuit may cause internal wire damage and current output break.   
Communication Mode (RS-485)
MODBUS ASCII/RTU Mode. Communication baud rate of 4800 / 
9600 / 19200 / 38400 / 57600 / 115200. For ASCII mode, format is 
7Bits, even, 1 stop bit (7 E 1), while RTU mode format is 8Bits, even, 
1 stop bit (8 E 1). The RS-485 is disabled when the DVP02AD-S is 
connected in series with an MPU. 
Connect to DVP-PLC MPU in 
Series 
If DVP02DA-S modules are connected to MPU, the modules are 
numbered from 0 – 7. 0 is the closest and 7 is the furthest to the 
MPU. 8 modules is the max and they do not occupy any digital I/O 
points of the MPU. 
3.2 Other 
Specification 
Max. Rated Consuming Power 
24 VDC (20.4VDC~28.8VDC) (–15%〜+20%), 3W, supply from 
external power 
Environment Condition and Wiring
Follow the DVP-PLC MPU 
Spec of 
Prevent
 Static Electricity 
All places between terminals and ground comply with the spec 
 
 
4
CR (Control Register) 
 
DVP-02DA Analog Output Module 
Explanation 
CR
No
RS-485 
Parameters 
Address 
Latched Register 
Name b15 
b14 
b13 
b12 
b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
#0
H 4032 
 
R Model 
type 
System used, data length is 8 bits (b7~b0). DVP-04AD model code=H 49 
Reserved CH2 
CH1 
#1
H 4033 
  R/W Output mode setting 
Output mode setting: factory setting is H0000. 
Mode 0: output voltage mode (0V~10V). 
Mode 1: output voltage mode (2V~10V). 
Mode 2: output current mode (4mA~20mA). 
Mode 3: output current mode (0mA~20mA). 
Mode 4: none use. 
#2 ~ #9 
Reserved 
#10
H 403C 
  R/W  CH1 output value 
#11
H 403D 
  R/W  CH2 output value 
The output setting range of channel CH1~CH2 is K0~K4000. Factory setting is K0 
and unit is LSB. 
#12~#21 Reserved 
#22
H 4048 
  R/W  To adjust OFFSET 
value of CH1 
#23
H 4049 
  R/W  To adjust OFFSET 
value of CH2 
It is used to set the OFFSET value of CH1~CH2. The setting range is 
K-2000~K2000. The factory setting is K0 and unit is LSB. 
#24 ~ #27 
Reserved 
#28
H 404E 
  R/W  To adjust GAIN 
value of CH1 
#29
H 404F 
  R/W  To adjust GAIN 
value of CH2 
It is used to set the GAIN value of CH~CH2. The setting range is K-1600~K8000. 
The factory setting is K2000 and unit is LSB. 
#30
H 4050 
 
R  Error status 
It is the data register to save all error status. Please refer to fault code chart for detail.
#31
H 4051 
  R/W Communication 
address setting   
It is used to set RS-485 communication address. The setting range is from 01 to 255 
and the factory setting is K1. 
#32
H 4052 
  R/W Communication 
Baud Rate setting 
It is used to set communication baud rate (4800, 9600, 19200, 38400, 57600, 
115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1), 
while RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). 
b0: 4800 bps (bit/sec).               b1: 9600 bps (bit/sec). (factory setting) 
b2: 19200 bps (bit/sec).                            b3: 38400 bps (bit/sec).                                   
b4: 57600 bps (bit/sec).              b5: 115200 bps (bit/sec). 
b6-b13: reserved.                                         
b14: exchange low and high byte of CRC check code (only for RTU mode) 
b15: ASCII / RTU mode selection 
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Reserved CH2 
CH1 
#33
H 4053 
  R/W Reset to factory 
setting and set 
characteristics 
adjustable priority 
Output latched setting, factory setting H0000. 
Give CH1 setting for example:   
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#22, CR#28). 
When b1=1, inhibit user to adjust OFFSET and GAIN value of CH1 (CR#22, 
CR#28). 
2. b1 means if characteristic register is latched. b1=0 (factory setting, latched), b1=1 
(not latched). 
3. When b2 is set to 1, all settings will be reset to factory setting.   
#34
H 4054 
 
R  Software version. 
In hexadecimal to display software version. For example: H 010A means 1.0A. 
#35~#48 System 
used 
  means latched. ,  ╳ means not latched.  
R means can read data by using FROM command via RS-485.   
W means can write data by using TO command via RS-485. 
LSB (Least Significant Bit):    1. Voltage output: 1
LSB
=10V/8000=2.5mV.    2. Current output: 1
LSB
=20mA/4000=5µA. 
Explanation: 
1. The content of CR#0 is model type, user can read the data from program to check if there is 
expansion module. 
2. CR#1 is used to set two internal channels working mode of analog output module. Every channel 
has four modes to set that can set individually. For example: if set CH1 to mode 2 (b2~b0=010), 
CH2 to mode 1(b5~b3=001). It needs to set CR#1 to H000A. The factory setting of CR#1 is H0000. 
3. CR#2 ~ CR#9, CR#12 ~ CR#21, CR#24 ~ CR#27 Reserved. 
4. CR #10 ~ CR#11 display CH1 and CH2 output signal. The setting range is K0~K4000.    Factory 
setting is K0 and unit is LSB. 
5. R#22 ~ CR#23 means the value to adjust OFFSET value of CH1 and CH2. The factory setting is K0 
and unit is LSB. If output value equal to 0 after calculating, the adjustable range of analog output 
voltage or current is -2000~+2000. 
Voltage adjustable range: -5V~+5V(-2000
LSB
~+2000
LSB
). 
Current adjustable range: -10mA~+10mA (-2000
LSB
~+2000
LSB
). 
6. R#28 ~ CR#29 means the value of adjust GAIN value of CH1 and CH2. The factory setting is K2000 
and unit is LSB. If output value equal to 2000 after calculating, the adjustable range of analog output 
voltage or current is -1600~+8000. 
Voltage adjustable range: -4V~+20V(-1600
LSB
~+8000
LSB
). 
Current adjustable range: -8mA ~+40mA (-1600
LSB
~+8000
LSB
). 
Please be noticed that GAIN VALUE – OFFSET VALUE = +400
LSB
 ~+6000
LSB 
(voltage or 
current). When
 
this value within this range, the resolution of the output signal will be thin and the 
value variation will be larger. When this value exceeds this range, the resolution of output signal 
will be thick and the variation of value will be smaller. 
7. CR#30 is the fault code. Please refer to the following chart. 
Fault Description 
Content b15~b8 b7
b6
b5
b4
b3
b2
b1
b0
Power Source Abnormal 
K1(H1) 
0 0 0 0 0 0 0 1 
Analog Input Value Error 
K2(H2) 
0 0 0 0 0 0 1 0 
Setting Mode Error 
K4(H4) 
0 0 0 0 0 1 0 0 
Offset/Gain Error 
K8(H8) 
0 0 0 0 1 0 0 0 
Hardware Malfunction   
K16(H10) 
0 0 0 1 0 0 0 0 
Digital Range Error 
K32(H20) 
0 0 1 0 0 0 0 0 
Average Times Setting Error 
K64(H40) 
0 1 0 0 0 0 0 0 
Command Error 
K128(H80) 
Reserved 
1 0 0 0 0 0 0 0 
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same time. 0 
means normal and 1 means fault happened.