Delta Electronics CME-COP01 Leaflet

Page of 1
http://www.delta.com.tw/industrialautomation/
 
5011648700-MPE0
2006-09-21
 
 
CANopen Network Adapter
 
Instruction Sheet 
 
Warning 
3
  This instruction sheet only provides descriptions on electricalspecifications, general specifications, installation and 
wiring and is only an introductory guide to CME-COP01. For more informaion on CANopen protocol, please refer to 
relevant literature. 
3
  CME-COP01 is an OPEN TYPE controller and therefore should be installed in an enclosure free of airborn dust, 
humidity, electric shock and vibration. The enclosure should protect non-maintenance staff from operating the device 
(e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur. 
3
  CME-COP01 is for controlling the machine and equipment in operation. In order not to damange it, please allow only 
qualified staff who is familiar with the structure and operation of it to intall, operate, wire and maintain it. 
3
  Please read this instruction carefully and follow this instruction to operation the device in order to prevent damages on 
the device or injuries to staff. 
3
  DO NOT connect input AC power supply to any of the input/output terminals; otherwise serious damage may occur. 
Check all the wiring again before switching on the power and DO NOT touch any terminal when the power is switched 
on. 
X
   
Introduction
 
1.1 Model 
Explanation 
 
Thank you for choosing Delta CME-COP01 CANopen communication module. CME-COP01 is specifically for 
connecting to CANopen communication module of Delta VFD-E AC motor drive. 
 
Functions of CME-COP01: 
™
 Supports Process Data Objects (PDO) Protocol 
™
 Supports Special Object Protocols (SOP) 
™
 Supports Service Data Object (SDO) Protocol 
™
 Supports Network Management (NMT) Protocol 
 
™
 Nameplate Explanation 
 
CMECOP01T6160001
MADE IN XXXXXX
MODEL:CME-COP01
USED ON:VFD-E SERIES
VERSION:XX.XX
Model name
Firmware version
Barcode & series No.
 
™
 Serial No. Explanation 
 
Production series
Production week
Production year (2006)
Production plant (Taoyuan)
Serial number of version
Production Model
COP01 00 T 6 16 0001
 
 
1.2 Product 
Profile 
           
1
2
7
6
3
4
5
 
Unit: mm 
 
 
 
c
 
COM port 
d
 
CANopen connection port 
e
 
RUN indicator 
f
 
ERROR indicator 
g
 
SP (Scan Port) indicator 
h
 
Baud rate switch 
i
 
Address switch 
 
 
Y
   
Specifications
 
CANopen Connection 
 
Interface Pluggable 
connector 
(5.08mm) 
Transmission method 
CAN 
Transmission cable 
2-wire twisted shielded cable 
Electrical isolation 
500V DC 
 
 
Communication 
 
Process Data Objects (PDO) 
Service Data Object (SDO) 
Synchronization (SYNC) 
Emergency (EMCY) 
Message type 
Network Management (NMT) 
 
 
10 Kbps 
20 Kbps 
50 Kbps 
125 Kbps 
250 Kbps 
500 Kbps 
800 Kbps 
Baud rate 
1 Mbps 
 
 
 
Product code 
Delta VFD-E AC motor drive        22 
Device type 
402 
Vendor ID 
477 
 
Environmental Specifications 
 
Noise Immunity 
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS(IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 
Environment 
Operation: 0°C ~ 55°C (Temperature), 50 ~ 95% (Humidity), Pollution degree 2;   
Storage: -40°C ~ 70°C (Temperature), 5 ~ 95% (Humidity) 
Vibration / Shock 
Resistance 
Standard: IEC1131-2, IEC 68-2-6(TEST Fc/IEC1131-2 & IEC 68-2-27 (TEST Ea) 
Certifications 
Standard: IEC 61131-2,UL508 
Z
   
Components
 
3.1  Pin Definition on CANopen Connection Port 
 
To connect with CANopen, use the connector enclosed with CME-COP01 or any connectors you can buy in the 
store for wiring. 
 
Pin 
Signal 
Content 
1 CAN_GND 
Ground / 0 V / V- 
2 CAN_L 
Signal- 
3 SHIELD 
Shield 
4 CAN_H  Signal+ 
5 -  Reserved 
 
1  2  3  4  5 
 
3.2  Baud Rate Setting 
Rotary switch (BR) sets up the communication speed on 
CANopen network in hex. Setup range: 0 ~ 7 (8 ~F are 
forbidden)
   
01
2
3
4
5
6
7 8 9 A
B
C
D
EF
BR
 
Example: If you need to set up the communication speed of CME-COP01 as 500K, simply switch BR to “5” 
 
BR Value 
Baud rate 
BR Value 
Baud rate 
0 10K 4 250K 
1 20K 5 500K 
2 50K 6 800K 
3 125K 7  1M 
 
L
 
The changed communication speed of CANopen is only valid when CME-COP01 is re-powered. When CME-COP01 is 
operating, changing the set value of communication speed is invalid. 
 
3.3 MAC 
ID 
Setting 
Rotary switches (ID_L and ID_H) set up the
 
Node-ID on 
CANopen network in hex. Setup range: 00 ~ 7F (80 ~FF 
are forbidden)
 
01
2
3
4
5
6
7 8 9 A
B
C
D
EF
01
2
3
4
5
6
7 8 9 A
B
C
D
EF
ID_H
ID_L
 
Example: If you need to set up the communication address of CME-COP01 as 26(1AH), simply switch ID_H to 
“1” and ID_L to “A”. 
 
Switch Setting 
Content 
0 … 7F 
Valid CANopen MAC ID setting 
Other 
Invalid CANopen MAC ID setting 
 
L
 
The changed values on ID_H and ID_L are only valid when CME-COP01 is re-powered. When CME-COP01 is 
operating, changing the address is invalid. 
 
 
3.4 CME-COP01 
Connector 
The communication port of CME-COP01 is used for 
connecting with Delta VFD-E AC motor drive.
 
PORT
 
 
 
 
 
 
 
3.4.1 COM PORT 
 
Port Pin Definition 
PORT Sketch 
Terminal No. 
Description 
1 N.C. 
2 N.C. 
3 N.C. 
4 DATA+ 
5 DATA- 
6 GND 
7 V+ 
1
2
3
4
5
6
7
8
 
8 N.C. 
 
L
 
The communication port supports RS-485/Modbus communication only. 
[
   
Connecting CME-COP01 with VFD-E
 
When CME-COP01 communicates with VFD-E through PORT, the power of CME-COP01 is supplied by VFD-E. 
See the figure below for the wiring of connection. 
 
RS-485 Communication 
(Using standard cable with RJ-45 connectors at its two ends is suggested)
 
CME-COP01 
RJ-45 (RS-485) 
VFD-E 
RJ-45 (RS-485) 
8  7  6  5  4  3  2  1 
8  7  6  5  4  3  2  1 
DATA-
DATA+
DATA-
DATA+
(5)
(4)
(5)
V+ (7)
GND (6)
(3) GND
(2) V+
 
\
   
LED Indicator Explanation & Troubleshooting
 
There are 3 LED indicators, RUN, ERROR and SP, on CME-COP01 to indicate the communication status of 
CME-COP01. 
5.1  RUN LED 
LED Status 
State 
Indication 
OFF 
No power 
No power on CME-COP01 card 
Single Flash 
(Green) 
STOPPED 
CME-COP01 is in STOPPED state 
Blinking 
(Green) 
PRE-OPERATIONAL 
CME-COP01 is in the PRE-OPERATIONAL state 
Green ON 
OPERATIONAL 
CME-COP01 is in the OPERATIONAL state 
Red ON 
Configuration error 
Node-ID or Baud rate setting error 
5.2  ERROR LED 
LED Status 
State 
Indication 
OFF 
No error 
CME-COP01 is working condition 
Single Flash 
(Red) 
Warning limit reached 
At least one of error counter of the CANopen 
controller has reached or exceeded the warning 
level (too many error frames) 
Double Flash 
(Red) 
Error control event 
A guard event or heartbeat event has occurred 
Red ON 
Bus-off 
The CANopen controller is bus-off 
5.3  SP LED 
LED Status 
State 
Indication 
OFF 
No Power 
No power on CME-COP01 card 
LED Blinking 
(Red) 
CRC check error 
Check your communication setting in VFD-E 
drives (19200,<8,N,2>,RTU) 
Red ON 
Connection failure/No connection 
1. Check the connection between VFD-E drive 
and CME-COP01 card is correct 
2. Re-wire the VFD-E connection and ensure 
that the wire specification is correct 
LED Blinking 
(Green) 
CME-COP01 returns error code 
Check the PLC program, ensure the index and 
sub-index is correct 
Green ON 
Normal 
Communication is normal 
5.4  LED Descriptions 
State 
Description 
LED ON 
Constantly on 
LED OFF 
Constantly off 
LED blinking 
Flash, on for 0.2s and off for 0.2s 
LED single flash 
On for 0.2s and off for 1s 
LED double flash  On for 0.2s off for 0.2s, on for 0.2s and off for 1s 
 
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or 
download the most updated version at http://www.delta.com.tw/industrialautomation