Raritan Computer EMX2-111 User Manual
Chapter 8: Managing External Devices
183
Hysteresis
Lower Warning Reset
Lower Warning Threshold
Hysteresis
Lower Critical Reset
Lower Critical Threshold
The hysteresis values define a reset threshold. For upper thresholds, the
measurement must fall past this reset threshold before a deassertion
event is generated. For lower thresholds, the measurement must rise
above this reset threshold before a deassertion event is generated.
measurement must fall past this reset threshold before a deassertion
event is generated. For lower thresholds, the measurement must rise
above this reset threshold before a deassertion event is generated.
What is Assertion Timeout?
When the assertion timeout is enabled, the EMX device asserts any
warning or critical condition only after a specified number of consecutive
samples that cross a particular threshold are generated. This prevents a
number of threshold alerts from being generated if the measurements
return to normal immediately after rising above any upper threshold or
dropping below any lower threshold.
warning or critical condition only after a specified number of consecutive
samples that cross a particular threshold are generated. This prevents a
number of threshold alerts from being generated if the measurements
return to normal immediately after rising above any upper threshold or
dropping below any lower threshold.