 Hysteresis 
Lower Warning Reset 
Lower Warning Threshold 
 
 
 Hysteresis 
Lower Critical Reset 
Lower Critical Threshold 
 
The hysteresis values define a reset threshold. For upper thresholds, the 
measurement must fall past this reset threshold before a deassertion 
event is generated. For lower thresholds, the measurement must rise 
above this reset threshold before a deassertion event is generated. 
 
What is Assertion Timeout? 
When the assertion timeout is enabled, the EMX device asserts any 
warning or critical condition only after a specified number of consecutive 
samples that cross a particular threshold are generated. This prevents a 
number of threshold alerts from being generated if the measurements 
return to normal immediately after rising above any upper threshold or 