Raritan Computer EMX2-111 User Manual

Page of 379
 
Appendix B: Integrating EMX and Asset Management Sensors with dcTrack 
 
 
345
 
 
12.  In the Numbering Offset field, select the starting number. For 
example, if you select 3, the first rack unit is numbered 3, the second 
is numbered 4, the third is numbered 5, and so on until the final 
number. 
13.  Indicate how the asset sensor is mounted in the rack in the 
Orientation field. The rack unit that is most close to the RJ-45 
connector of the asset sensor will be marked with the index number 
1 in the web interface. 
For the latest version of asset sensors with a built-in tilt sensor, it is 
NOT necessary to configure the orientation setting manually. The 
EMX device can detect the orientation of the asset sensors and 
automatically configure it. 
  Top Connector: This option indicates that the asset sensor is 
mounted with the RJ-45 connector located on the top. 
  Bottom Connector: This option indicates that the asset sensor is 
mounted with the RJ-45 connector located at the bottom. 
14.  To change the LED color denoting the presence of a connected tag, 
either click a color in the color palette or type the hexadecimal RGB 
value of the color in the "Color with connected Tag" field. 
15.  To change the LED color denoting the absence of a connected tag, 
either click a color in the color palette or type the hexadecimal RGB 
value of the color in the "Color without connected Tag" field. 
16.  Click OK to save the changes. 
See the EMX Help for additional information on using the EMX device. 
 
Setting EMX Asset Sensor LED Colors 
In the EMX web interface, a rack unit refers to a tag port on the asset 
sensor. You can name a specific rack unit, or change its LED color 
settings so that this LED behaves differently from others on the same 
asset sensor. 
 
To change an LED's settings: 
1.  If you have not already done so, log in to the EMX. 
2.  Connect the asset sensor to the EMX if it is not already.  
3.  Click on the Feature Ports folder in the navigation tree to expand it. 
4.  Click the desired asset sensor. The page specific to that asset 
sensor opens in the right pane, showing the asset sensor settings 
and information of all rack units (tag ports). 
Note: You can also access this dialog by double-clicking the asset 
sensor shown on the Dashboard page. 
5.  Select the rack unit whose LED settings you want to change.