Raritan Computer EMX2-111 User Manual

Page of 379
Chapter 2: Installing and Configuring the EMX Device 
 
28
 
 
 
 
To connect asset sensors to the EMX-888 device: 
1.  Affix the adhesive end of an asset tag to each IT device through the 
tag's tape. 
2.  Plug the connector on the other end of each asset tag into the 
corresponding tag port on the asset sensor. 
3.  Connect one end of a Cat5e/6 cable to the RJ-45 connector on the 
MASTER asset sensor, and then connect the other end of the cable 
into a FEATURE port on the EMX-888.  
4.  If needed, repeat the above steps to connect additional asset 
sensors to the rest of FEATURE ports.  
5.  Configure the asset sensor. See 
Configuring the Asset Sensor
 (on 
page 330). 
 
Connecting AMS-M2-Z Asset Sensors (Optional) 
The AMS-M2-Z is a special type of asset sensor that functions the same 
as regular MASTER asset sensors with the following differences: 
 
It provides two RJ-45 connectors 
 
Multiple AMS-M2-Z asset sensors can be daisy chained 
 
Only two tag ports are available on each AMS-M2-Z so only two 
asset tags can be connected 
This product is especially useful for tracking large devices such as SAN 
boxes in the cabinet. 
 
Item 
Description 
RJ-45 connectors 
Tag ports 
 
To connect the AMS-M2-Z asset sensors to the EMX: 
1.  Connect the AMS-M2-Z to the EMX via a Category 5e/6 cable. 
a.  Connect one end of the cable to the RJ-45 port labeled "Input" 
on the AMS-M2-Z.