Promise Technology M300p User Manual

Page of 322
VTrak M-Class Product Manual
230
Replace Cache Battery – M500f/i/p
The cache battery is located in the Cooling Unit 1 (the left one). The battery is 
replaced as an individual part. No tools are required for this procedure.
Note that the Battery LED on Cooling Unit 2 is always dark.
To replace a cache battery, do the following:.
1.
Verify that the battery LED is amber or red (above). 
Cautions
Try reconditioning the battery before you replace it. See 
“Battery” on page 120 for more information.
Installing an incorrect replacement battery may result in an 
explosion.
Dispose of used batteries according to the instructions that 
accompany the battery.
While the battery is removed, your system will be vulnerable 
to a power failure. Temporarily set your cache policy to write-
through before starting this procedure. See “Logical Drive 
Settings” on page 144 (W
ebPAM PROe) or “Logical Drive 
Settings and Functions” on page 189. (C
LU).
If power service has failed, do not remove the cooling unit if 
the Controller’s Dirty Cache LED is flashing. See “Unsaved 
Data in the Controller Cache” on page 295.
Battery LED