1 General
1.1 Interface hardware
To communicate with a host computer, an SPS, etc., the controllers R2600 / 01 must be equipped with marking F1. In this case, the controllers are 
equipped with a serial interface having the following data:
• Level types
RS-232 and RS-485 (two-wire)
in the unit selectable 
• Baud rate
9600 bd
• Character format 8 data bits, 1 parity bit, 1 stop bit
• Parity
Even
• Maximum number of equipment on the bus:
32
• With RS-485 bus operation, each connected R2600/01 must 
have a different interface address (Addr = 0 ... 250) 
(see operating instructions 3-348-778-15).
1.2 Communications protocol
The transmission protocol used complies with DIN draft 19244. The R2600 / 01 uses only a partial amount of the defined functions which are 
described below.
RS-232
RS-485