ICP DAS USA 8830 User Manual

Page of 90
 
#AASi 
Command 
#AASi 
Description  Reads the analog input or counter/frequency module data for all 
channels from specified slot in the I-8000 unit.   
#AASi[CHK](cr) 
A delimiter character 
AA 
A 2-character HEX module address for the 
specified I-8000 system ,ranging from 01 to FFh 
Si 
The specified slot number. i = 0 to 3 (4 slots) or   
i = 0 to 7 (8 slots) 
[CHK] 2-characters 
of 
Syntax 
(cr) 
Character Return(0x0D) for denote the end of 
command 
Valid Command 
>(data)[chk](cr) 
Invalid Command 
?AA[CHK](cr) 
Syntax error or communication error may get no response. 
A delimiter for valid command 
A delimiter for invalid command 
AA 
A 2-character HEX module address 
(data) 
A return string from the RTD input module in 
engineering mode. 
[CHK] A 
2-character 
 
(cr) 
Carriage Return(0x0D) to denote the end of 
response 
Command 
#01S3 
Response 
>+2.1234+2.1234 +2.1234 +2.1234 (cr) 
Example 
Description 
The data read from analog data input module 
i-87013 (4 channels analog input module) in slot 3 
of the I-8000 system at address 01h is 
+2.1234+2.1234 +2.1234 +2.1234
Note: i-87013 
Π4-Channel RTD Analog Input Module 
i-8017H 
ΠFast 8-Channel mV/V/mA Analog Input Module 
i-87017 
Π8-Channel mV/V/mA Analog Input Module 
i-87018 
Π8-Channel mV/V/mA and Thermocouple Analog Input 
Module 
i-8080 
Π8-Channel Counter/Frequency Module 
 
8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10    -----    72