Output Processing Functions
5-32
■ Control output CH1
Control output CH1 is processed as shown below.
● Current output (with setup data 
C21
set to 1)
Chapter 5. FUNCTIONS
Initialization of PID 
control computation
Output deviation limiter
PID control computation Setting: PID parameter 
P
 / 
l
 / 
d
 / 
rE 
(for CH1)
Setup data 
C23
Setting: variable parameter 
PA17
PA43
Setting: variable parameter 
PA14
Upper and lower output limiter
Setting: PID parameter 
oL
 / 
oH 
(for CH1)
ON-OFF control computation
Setting: variable parameter 
PA16
              PID parameter 
oL 
oH 
(for CH1)
During ON-OFF control
AT computation
Setting: variable parameter 
PA08
PA09
PA10
AT executed
Manipulated variable during overrange
Setting: setup data 
C33
C34
During overrange
Manipulated variable in READY mode
Setting: setup data 
C32
In READY mode
MANUAL Manipulated variable
In MANUAL mode
Preset MANUAL value
Manipulated variable (MV1)
Output 1
Proportional current output: 4 to 20mA
Setting: setup data 
C35
C36