Moxa Technologies IA5150 User Manual

Page of 108
NPort IA5150/5250 Series User’s Manual 
Web Console Configuration 
 
5-11
Baud rate 
Setting 
Factory Default 
Necessity 
110 bps to 230400 bps 
115200 bps 
Required 
Data bits   
Setting 
Factory Default 
Necessity 
5, 6, 7, 8 
Required 
When the user sets Data bits to 5 bits, the Stop bits setting will automatically change to 1.5 bits. 
Stop bits   
Setting 
Factory Default 
Necessity 
1, 2 
Required 
Stop bits will be set to 1.5 when Data bits is set to 5 bits. 
Parity 
Setting 
Factory Default 
Necessity 
None, Even, Odd, Space, Mark 
None 
Required 
Flow control 
Setting 
Factory Default 
Necessity 
None, RTS/CTS, DTR/DSR, Xon/Xoff 
RTS/CTS 
Required 
FIFO 
Setting 
Factory Default 
Necessity 
Enable, Disable 
Enable 
Required 
NPort IA5150/5250’s serial ports provide a 16-byte FIFO both in the Tx and Rx directions. To 
prevent data loss during communication, disable the FIFO setting when your serial device does not 
have a FIFO. 
Interface 
Setting 
Factory Default 
Necessity 
RS-232 
RS-422 
2-wire RS-485 
4-wire RS-485 
RS-232 Required 
Operating Settings 
 
Click on Operating Settings, located under Main Menu, to display the operating settings for both 