RS-485 Connections
 ION 7500 / ION 7600 User’s Guide
Page 128
Chapter 5 - Features and Applications 
RS-485 Connections
Refer to the “Hardware Reference” chapter for the ION 7500 and ION 7600 meters’ 
RS-485 specifications.
RS-485 connections are made via the captured-wire connectors on the rear of the 
meter. Up to 32 devices can be connected on a single RS-485 bus. Use a good 
quality shielded twisted pair cable for each RS-485 bus, AWG 22 (0.5 mm
2
) or 
larger. The overall length of the RS-485 cable connecting all devices cannot exceed 
4000 ft. (1219 m). The RS-485 bus may be configured in straight-line or loop 
topologies.
Straight-Line Topology 
Loop Topology 
General Bus Wiring Considerations
Devices connected on the bus, including the meter, converter(s) and other 
instrumentation, must be wired as follows: 
Connect the shield of each segment of the cable to ground at one end only
Isolate cables as much as possible from sources of electrical noise.
Use an intermediate terminal strip to connect each device to the bus. This allows 
for easy removal of a device for servicing if necessary.
Install a ¼ Watt termination resistor (R
T
) between the (+) and (-) terminals of the 
device at each end point of a straight-line bus. The resistor should match the 
nominal impedance of the RS-485 cable (typically 120 ohms – consult the 
manufacturer’s documentation for the cable’s impedance value).