Calibration Pulser Module
 ION 7500 / ION 7600 User’s Guide
Page 220
Digital and Analog I/O Technical Note
Detailed Operation
The following example illustrates the basic operation of a Digital Output module. 
The input in the figure could be any of the SourceForce ONForce OFF, or Normal 
inputs. The EvLog Mode and the Port setup registers could be set to whatever is 
appropriate (they do not affect the output values of the module). Similarly, the 
Mode and Event output registers contain whatever is appropriate. 
When specifying the Polarity setup register, you must consider the characteristics 
of the external output device. If you have defined different 
ON
 or 
OFF
 labels for the 
State output register, you should consider the characteristics of the output device 
and the Polarity setting.
Calibration Pulser Module
The Calibration Pulser module is a highly accurate energy pulser often used for 
verifying calibration on ION revenue meters. This module can serve as an 
intermediary between the power (kW, kVAR or kVA) outputs of the Meter Units 
Power Meter module and an ION meter’s hardware output channel.
The module integrates the instantaneous power inputs and then outputs complete 
pulses or KYZ transitions to a hardware channel. Using the Calibration Pulser 
module setup registers, you must specify the output mode, output rate (Kt), the 
output pulse width or minimum duration between KYZ transitions, and the 
hardware port where the pulses appear.
Calibration Pulser Module Setup Registers
Setup Register
Description
Output Mode
Specifies whether the output is a complete pulse (PULSE) or a change of 
state transition (KYZ)
Pulse Width
Specifies the width (on-time) of the output pulse (e.g. how long an LED is lit 
or relay is open) 
Kt
Defines how much energy is accumulated by the module before an output is 
sent to the hardware channel
Integration Mode
Defines the mode of integration 
Ports
Defines the hardware port where the output appears