Setting Up your WebMeter Network
 ION 7500 / ION 7600 User’s Guide
Page 274
WebMeter Internal Web Server Feature Technical Note
Setting Up your WebMeter Network
 
This section presents information geared to the network administrator who sets up 
the corporate network for web browser access to the meter. The required network 
components for using WebMeter are described, as well as the configuration of 
network settings. 
Configuring Meter Network Settings
A WebMeter-enabled device resides on an Ethernet network and requires an IP 
Address and other network settings to define its location on the network, and to 
interact properly with other network devices. These network settings can be set 
manually with the meter’s front panel, or automatically with a BootP Server.
To learn how to configure meter network settings manually with the meter’s front 
panel, refer to Network Settings in your meter’s Installation and Basic Setup 
Instructions
.  
Automatic Configuration via a BootP Server 
BootP
 
(Bootstrap Protocol) is a protocol that automatically configures a device’s 
(e.g. meter’s) network settings without user involvement. 
The BootP server is managed by the network administrator, who allocates the 
meter IP address and other network settings to the BootP server. When this is 
completed, and the meter is booted up, the BootP server automatically assigns the 
IP address and other network settings to the meter.    
When the meter is in BootP mode, it does not need to be manually re-booted for an 
IP address change. Since most power meters cannot be easily rebooted on demand, 
the meter has been set up to poll the BootP server every eight hours for an IP 
address. If the IP address is changed on the BootP server, then the meter obtains 
the new address at the next polling interval. 
N
OTE
Depending on your meter and meter firmware version, BootP may be enabled by default; check your
meter’s 
Basic Setup and Installation Instructions
. You can enable BootP with the meter’s front panel or
with ION software.    
Preparing the BootP Server to automatically configure network settings:
1.
Set up the BootP server on the same Ethernet network as the meter you wish 
to access using a web browser. Follow the documentation packaged with the 
BootP software for the correct installation.
2.
Enter the meter Ethernet MAC address in the BootP database.