Magnitude of Voltage Supply
 ION 7500 / ION 7600 User’s Guide
Page 304
Power Quality: ION Meters and EN50160 Technical Note
Magnitude of Voltage Supply
Each measurement is the mean of RMS voltage for each phase over fixed 10-minute 
intervals. The nominal value is defined by the Sag/Swell module’s Nom Volts setup 
register. 
N
OTE
Nom Volts
 is typically setup when the meter is placed into service; if 
Nom Volts
 has not been set, enter a
value for your system’s nominal voltage. This value will be used in all EN50160 compliance calculations.
Observation period of one week with fixed steps of 10 minutes.
= number of 10-minute intervals in which the supply voltage is within ±15% of 
nominal.
N
1
 = number of intervals in which the supply voltage differs more than 10% 
from nominal and supply voltage is within ±15% of nominal.
Supply voltage complies with the standard if N
1
/N <= 5% during the observation 
period (1 week by default).
EN 50160 data (current observation period): The meter generates the N and N
1
 
counts for each phase as described above. These counters are reset at the beginning 
of the next observation period.
EN 50160 data (previous observation period): The meter stores the N and N
1
 
counter values at the end of each observation period before these counters are 
reset. These 6 registers are also stored in a data recorder for each observation 
period.
Events: The meter creates a message in the Event log every time the N
1
 counter for 
each phase increases.
Parameter data: The meter can be enabled to record the 10-minute mean, ½ cycle 
minimum and ½ cycle maximum values of supply voltage for each phase into a 
data recorder every 10 minutes.