Default Meter Functionality
 ION 7500 / ION 7600 User’s Guide
Page 50
Chapter 3 - Default Meter Functionality 
Default Meter Functionality
The following sections describe the default functionality defined by your meter’s 
framework. With each advancement of firmware, there are changes to the 
framework, so your meter operation may differ slightly from what is presented.
The ION Device Templates documentation lists all the ION modules available in the 
current version of your meter, lists the total number of each ION module, and 
shows the ranges or options available for each module’s setup registers. The ION 
Devices Templates
 documentation is available at www.pwrm.com.
Basic Setup
Basic configuration of the meter is provided by the Power Meter module. The 
Power Meter module is the main connection between the power system 
measurements and all other ION modules in the device. This module reports the 
values for all voltage, current and power measurements.
The Power Meter module’s setup registers describe details of the power system 
being monitored. Many of the Power Meter module’s setup registers are 
configured when the meter is initially put into service, although the device cannot 
operate properly until the Volts Mode and PT and CT ratios are set. Some registers 
may need to be changed to refine the device’s operation. 
1
The registers are typically set when the device is commissioned. Changing the values of these registers 
while the device is in service is not recommended.
Setup 
Register
Function
Default
Volts Mode 
1
The power system’s configuration – WYE, DELTA, Single, etc
4W-
WYE
PT Prim 
1
The Potential Transformer’s primary winding rating for V1, V2 and V3
120
PT Sec 
1
The Potential Transformer’s secondary winding rating for V1, V2 and V3
120
CT Prim 
1
The Current Transformer’s primary winding rating for I1, I2 and I3
5
CT Sec 
1
The Current Transformer’s secondary winding rating for I1, I2 and I3
5
V4 Prim 
1
The Potential Transformer’s primary winding rating for V4
120
V4 Sec 
1
The Potential Transformer’s secondary winding rating for V4
120
I4 CT Prim 
1
The Current Transformer’s primary winding rating for I4
5
I4 CT Sec 
1
The Current Transformer’s secondary winding rating for I4
5
I5 CT Prim 
1
The Current Transformer’s primary winding rating for I5
5
I5 CT Sec 
1
The Current Transformer’s secondary winding rating for I5
5
Vn Polarity
The polarity of the Potential Transformer on Vn
Normal
In Polarity
The polarity of the Current Transformer on In
Normal
Phase Order
The expected rotation of the voltage phases (ABC or ACB)
ABC
Phase Lbls
The phase label format assigned to the outputs (ABC, RST, XYZ, RYB, 
RWB or 123)
ABC