Multi-Tech Systems 7500 User Manual

Page of 372
ION 7500 / ION 7600 User’s Guide
Data Logging Setup
Chapter 3 - Default Meter Functionality 
Page 53
Data Logging Setup
The data recording frameworks contain Data Recorder modules, Waveform 
Recorder modules, and Periodic Timer modules. Data Recorder and Waveform 
Recorder modules are responsible for logging the power system data. The Periodic 
Timer modules control the recording frequency of the recorder modules to which 
they are linked.
Default Logging Capacity
The following table summarizes the default recording depths and recording 
intervals of the various Data recorders and Waveform recorders in the meter.
Procedures for changing the logging depth and the frequency of logging are follow 
below.
Changing the Log Depths
Change the value in the Data Recorder’s Depth setup register to increase the 
number of records stored in the recorder. The RecordMode setup register controls 
how the Data Recorder will overwrite old records; refer to the Data Recorder 
module description in the online ION Programmer’s Reference before changing this 
setup register.
Log name
Depth
Interval
Revenue Log
3360
900 seconds (15 minutes)
Loss Log
3360
900 seconds (15 minutes)
TOU Data Logs (6 data recorders)
20
50 
(ION 7500)
(ION 7600)
Triggered on demand
Historic Logs (3 data recorders)
760
900 seconds (15 minutes)
Harmonics Logs (2 data recorders)
190 
840 
(ION 7500)
(ION 7600)
3600
Waveform recording (waveform recorders:
6 for ION 7500, 14 for ION 7600)
5       
15     
ION 7500)
(ION 7600)
Triggered on demand
Report Generator Log (EgyDmd Log)
192   
3360 
ION 7500)
(ION 7600)
900 seconds (15 minutes)
Sag/Swell Log
100
Triggered on demand
Transient Log (ION 7600 only)
100
Triggered on demand
Event Log (Event Log Controller module)
500
Triggered on demand
EN50160 Logs (22 data recorders)
(ION 7600 only)
10
Daily, weekly, 10 minutes, ...