Multi-Tech Systems 7500 User Manual

Page of 372
Using the DNP 3.00 Protocol
 ION 7500 / ION 7600 User’s Guide
Page 80
Chapter 3 - Default Meter Functionality 
Using the DNP 3.00 Protocol
The Distributed Network Protocol Version 3.00 (DNP 3.00) is an open protocol 
used in the electric utility industry for communications and interoperability 
among substation computers, Remote Terminal Units (RTUs), Intelligent 
Electronic Devices (IEDs, e.g. meters), and Master Stations. The meter can be 
integrated into a DNP network using the DNP Slave Import, Export and Options 
modules.
The Factory DNP 3.00 Configuration
The meter’s factory configuration makes various parameters available to export 
through DNP 3.00. There is no factory-configured functionality for importing DNP 
3.00 data into the meter.
ION modules are linked to DNP Slave Export modules which convert the ION 
data into the appropriate DNP objects. These objects are available through the ION 
7500 or ION 7600 meter’s communications port that is configured to use the DNP 
3.00 protocol. The DNP Options module sets global options for all of the DNP 
Slave Export modules.
The meter is shipped from the factory with the following DNP static objects 
defined. The following objects are returned in response to a Class 0 Poll. Note that 
the protocol of the desired communications port must set to “DNP 3.00” before the 
meter will respond to DNP master requests.
ION meter
DNP Slave Export
Module
Power Meter
Module
Vln a
DNP objects
DNP Options module
sets global options for
all DNP modules
Set the COM
port to DNP 3.0
protocol
Data is available
to DNP devices
Measured data is linked to the
DNP Slave Export module’s input
Communications Port
DNP Options
Module