Event Logging
 ION 7500 / ION 7600 User’s Guide
Page 150
Chapter 5 - Features and Applications 
Event Logging
Events produced by a meter’s various ION modules are prioritized and grouped 
to facilitate custom logging. Each event is assigned a priority group number based 
on its type and severity. 
ION Event Priority Groups
Some event groups are preset with a Priority Number as shown in the table below. 
You can also define your own priority number for some modules. Priority 
numbers from 128-191 appear in the global even log viewer in ION Enterprise 
software. Priority numbers from 192-255 are logged, initiate a beep and cause the 
window to flash. You can customize these responses to display messages or 
perform netsend messages, for example.
The Event Log Controller module allows you to set a priority cutoff for event 
logging. Any events with a priority number greater than the cutoff value are 
logged, and events with lower priorities are discarded. Refer to the individual 
module descriptions and the Event Log Controller module description in the
online ION Programmer’s Reference for more details.
Event Group
Description
Priority Number
Reset
Module reset or re synchronized
5
Setup Change
Module setup changes (setup register changes, label changes, input handle changes)
10
Input Register Change
Inputs of certain modules change value (ie, input to And/Or module changes)
15
I/O State Change
I/O state changes (ie, relay closes)
20
Information
Module produces important user information
25
Warning
Module produces a warning
30
EN50160 Event
(ION 7600 only)
An EN50160 Counter (N
1
 or N
2
) increases
50
Failure
A failure has occurred
255
Setpoint
Setpoint condition goes Active or Inactive (ie, Sag/Swell module detects a disturbance)
programmable via
module setup