Multi-Tech Systems 7600 User Manual

Page of 372
ION 7500 / ION 7600 User’s Guide
Additional Revenue Metering Security
ION Security Technical Note
Page 263
3.
Select the user name you want from the available list. Click the Edit button. The 
following window appears:
4.
Click Time Sync Access from the available settings list. If you want to allow this 
user to send time synchronization signals to the meter, ensure the setting reads 
Yes. To change the setting, click the Edit button and make the appropriate 
changes.
 
Additional Revenue Metering Security
To meet government regulations and utility security requirements, the revenue 
meter incorporates additional security systems:
a hardware-locked security system that prevents modification of revenue 
quantities after the meter is sealed.
a traditional anti-tamper mechanical seal on the meter base unit.
Hardware Lock Security
The hardware-locked security feature is an ordering option for some ION meters. 
This hardware lock is factory set; to make configuration changes to billing 
parameters on a hardware-locked meter, you must first place the meter in TEST 
mode. Refer to your meter’s User’s Guide for the location of the test mode button. 
In all cases, the TEST mode button is located under the anti-tamper sealed outer 
cover.
In certain countries the meter is no longer revenue certified if the hardware lock is 
broken.
Typical values that are protected include:
kWh, kVARh, kVAh delivered, received, del-rec, del+rec.
kW, kVAR, kVA Thermal and Sliding Window demand min and max values.
Digital Outputs controlling the energy pulsing applications.
All Power system settings, including PT an CT ratios.