ION 7500 / ION 7600 User’s Guide
Pasting the Modbus Master Framework into the Meter
Sub-Metering with a Modbus Master Technical Note
Page 327
Pasting the Modbus Master Framework into the Meter
This section describes how to paste the Modbus Master framework into the meter.
C
AUTION
The Modbus Master framework is designed to work with meters that use their factory default framework.
If you paste the Modbus Master framework into a meter that is not using its default configuration, the
custom configuration on your meter can be destroyed.
1.
Ensure that the Modbus Master framework (Modbus_Master.fwn) is located 
in your frameworks directory (C:\ION Enterprise\config\fmwk\nd).
2.
Connect to your Modbus Master device in Designer. 
3.
Open the Options menu and verify that the Show Toolbox menu item is 
checked.
4.
Double-click on the Frameworks folder to access the Advanced Configuration 
folder.
N
OTE
Before you paste in the new framework, click on an empty area of the screen. This ensures that no
modules are selected.
5.
Click on the Edit menu and select Paste From Framework. 
6.
Select the Modbus Master framework and click Open. 
7.
In the Paste Summary dialog box, click OK.  This will “free paste” the Modbus 
Master framework into the meter.  When the pasting is completed, a new folder 
called Modbus Master Framework appears.
N
OTE
Refer to the section, “Multiple Modbus Master Devices” if you plan to use this framework in several 
Modbus Master devices.
8.
Once you have returned to the main window in Designer, click Send and Save 
to save your changes.