ION 7500 / ION 7600 User’s Guide
Meter Resets
Chapter 2 - Using The Front Panel 
Page 43
Meter Resets
The Meter Resets menu item allows you to clear the cumulative parameters stored 
by the meter. You are required to enter a valid meter password before executing 
any meter resets.
Factory Resets
This sub-menu contains the following default resets:
peak dmd rset
The Peak Demand Reset allows you to clear the peak demand values logged in the 
meter. When the meter is in test mode, the Demand Reset object clears the Revenue 
Test Mode demand parameters. 
N
OTE
See “Revenue Measurements” on page 97 for more information about 
TEST
 mode.
By default, there is a 25 day Demand Lockout Time. This is the minimum time 
allowed between consecutive demand resets. Any attempts to perform a demand 
reset before the lockout time has expired will be ignored. See “Demand Setup 
Menu” on page 34 for det
ails about reconfiguring the default Demand Lockout.
MNMX
 
RSET
The Minimum/Maximum Reset allows you to clear all accumulated minimum and 
maximum values stored in the meter.
HARM
 
MNMX
 
RSET
The Harmonics Minimum/Maximum Reset allows you to clear all accumulated 
minimum and maximum harmonics values stored in the meter.
MASTER
 
RESET
The Master Reset control allows you to clear all the cumulative and derived 
quantities from the meter (including demand, peak demand, energy, revenue, and 
test mode parameters), clear the meter’s event and waveform logs, and reset the 
meter’s Data Recorder modules.
C
AUTION
The Master Reset operation will clear all billable quantities from the meter, all logged data from the
meter’s event and waveform logs, and all data recorders. Carefully consider the implications of
performing a Master Reset before proceeding.
DI
 
COUNT
 
RESET
The DI Count Reset allows you to clear the Digital Input Status Change counter. 
By default, the number of status changes of each digital input is shown in the
D Inputs front panel display as well as in the Vista Digital Inputs/Outputs diagram.